Technical Data¶
The System Data of AC500 and S500 are valid for standard version System Data AC500.
The System Data of AC500-XC are valid for the XC version System Data AC500-XC.
Only additional details are therefore documented below.
Parameter | Value |
---|---|
Connections of terminals | The terminals 1.8, 4.8…7.8, 1.9, 4.9…7.9, 4.0…4.7, 7.0…7.7 are electrically interconnected within the TF5x1_CMS. Terminals 1.8, 4.8…7.8: Process voltage L+ = +24 V DC Terminals 1.9, 4.9…7.9: Process voltage M = 0 V Terminals 4.0…4.7, 7.0…7.7: Analog shield clamps SH Terminal 1.0: FE shield clamp of encoder |
Protection against reverse voltage | Yes |
Rated protection fuse at UP | 10 A fast |
Rated value | 24 V DC |
Max. ripple | 5 % |
Current consumption from L+ (FM502_CMS and PM592_ETH, no Communication Module) | Max. 0.43 A + max. 0.5 A per output |
Inrush current from L+ (at power up, FM502_CMS and PM592_ETH, no Communication Module) | 1.2 A:sup:2s |
Electrical isolation | Yes, PM592_ETH and FM502_CMS to other I/O Bus Modules |
Max. power dissipation within the FM502_CMS | 6.5 W (outputs unloaded) |
All I/O channels are protected against reverse polarity, reverse supply, short circuit and continuous overvoltages up to 30 V DC.
For maritime applications a metal cabinet is required
Parameter | Value |
---|---|
Weight FM502-CMS | 215 g |
Weight FM502-CMS-XC | 220 g |
Mounting position | Horizontal Vertical with derating: max. temperature 40 °C |
Cooling | The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet. |
Deratings for operation of FM502_CMS-XC between +60 °C and +70°C | No use of 24 V encoder mode. Analog inputs: maximum number of configured input channels limited to 75 % per group AI0…AI7 and AI8…AI15. |
Parameter | Value |
---|---|
Number of supplies | 1 |
Connections | Terminal 1.7 |
Rated value | 5 V DC (+/- 5%) |
Resistance to feedback against reverse polarity | No |
Resistance to feedback against 24 V signals | Yes |
Output current | 100 mA max. |
Output diagnosis | Yes, with diagnosis LED and error message |
Parameter | Value | |
---|---|---|
Number of channels | 2 + 2 configurable inputs/outputs | |
Connections | Terminals 2.8, 2.9, 3.8, 3.9 | |
Reference potential | Terminals 1.9, 4.9, 5.9, 6.9, 7.9 for M (0 V) | |
Indication of the input signals | One yellow LED per channel, the LED is ON when the input signal is high (signal 1) | |
Input type acc. to EN 61131-2 | Type 1 | |
Input delay (0->1 or 1->0) | Typ. 8 ms, configurable from 0.1 to 32 ms | |
Input signal voltage | 24 V DC | |
Signal 0 | -3 V…+5 V Due to the direct connection to the output, the demagnetizing varistor is also effective at the input. This is why the difference between L+ and the input signal may not exceed the clamp voltage of the varistor. The varistor limits the voltage to approx. 36 V. The input voltage must range from - 12 V to + 30 V when L+ = 24 V and from - 6 V to + 30 V when L+ = 30 V. |
|
Undefined signal | > +5 V…< +15 V | |
Signal 1 | +15 V…+30 V | |
Ripple with signal 0 | Within -3 V…+5 V* | |
Ripple with signal 1 | Within +15 V…+30 V | |
Input current per channel | ||
Input voltage +24 V | Typ. 5 mA | |
Input voltage +5 V | > 1 mA | |
Input voltage +15 V | > 5 mA | |
Input voltage +30 V | < 8 mA | |
Max. cable length | ||
Shielded | 1000 m | |
Unshielded | 600 m |
Parameter | Value | |
---|---|---|
Number of channels per module | 2 configurable inputs/outputs | |
Connection | Terminal 3.8, 3.9 | |
Reference potential | Terminals 1.9, 4.9, 5.9, 6.9, 7.9 for M (0 V) | |
Indication of the output signal | One LED per channel | |
Power supply voltage | Terminals 1.8, 4.8, 5.8, 6.8, 7.8 for L+ (+24 V) | |
Output voltage for signal 1 | L+ (-0.8 V) | |
Output delay (0->1 or 1->0) | On request | |
Output current | ||
Rated value, per channel: 500 mA at UP = 24 V | 500 mA at L+ = 24 V | |
Maximum value: 1 A | 1 A | |
Leakage current with signal 0 | < 0.5 mA | |
Demagnetization when inductive loads are switched off | With varistors integrated in the module | |
Switching frequency | ||
With resistive load | On request | |
With inductive loads | Max. 0.5 Hz | |
With lamp loads | Max. 11 Hz with max. 5 W | |
Short-circuit proof / overload proof | Yes | |
Overload message (I > 0.7 A) | Yes, after ca. 100 ms | |
Output current limitation | Yes, automatic reactivation after short-circuit/overload | |
Resistance to feedback against 24V signals | Yes | |
Max. cable length | ||
Shielded | 1000 m | |
Unshielded | 600 m |
Circuitry of a digital input/output with the varistors for demagnetization when inductive loads are switched off.
Parameter | Value | |||
---|---|---|---|---|
Number of channels per module | 3 (sampled synchronously with IEPE inputs) | |||
Connection | Terminals 1.1, 1.2, 1.3, 1.4, 1.5, 1.6 | |||
Reference potential | Terminals 1.9, 4.9, 5.9, 6.9, 7.9 for M (0 V) | |||
Indication of the input signals | One LED per channel | |||
Resolution | 32 Bit | |||
Input type | 24 V DC | 5 V DC | Differential RS-422 and 1 Vpp sine | |
Input current per channel | ||||
Input voltage + 24 V | Typ. 6 mA | |||
Input voltage + 5 V | > 1 mA | |||
Input voltage + 15 V | > 5 mA | |||
Input voltage + 30 V | < 8 mA | |||
Input type acc. to EN61131-2 | Type 1 | |||
Input frequency max. (frequency measurement) | 100 kHz (accuracy -0 %/+3 %) | |||
Input signal voltage | 24 V DC | 5 V DC | Differential | |
Input frequence max. | 300 kHz | 1 MHz | 1 MHz | |
Signal 0 | -30 V…+5 V | -30 V…+0.8 V | =< 200 mV | |
Undefined signal | > +5 V… < +15 V | > +0.8 …< +2.0 V | - | |
Signal 1 | +15 V…+30 V | +2.0 V…+30 V | => +200 mV | |
Ripple with signal 0 | Within -30 V…+5 V | Within -30 V…+0.8 V | - | |
Ripple with signal 1 | Within +15 V…+30 V | Within +2.0 V…+30 V | - | |
Max. cable length, shielded (depending on sensor) | 300 m | 100 m |
Parameter | Value |
---|---|
Number of channels | 1 |
Connection | Terminals 1.3, 1.4 |
Reference potential | Terminals 1.9, 4.9, 5.9, 6.9, 7.9 for M (0 V) |
Indication of output signal | One LED per channel, the LED is ON when SSI CLK output B is active |
Differential output voltage for signal 1 | > 2.4V at 10 mA |
Differential output voltage for signal 0 | ≤ -2.4 V at 10 mA |
Output delay (0->1 or 1->0) | Max. 0.35 µs |
Output current | ≤ 10 mA |
Switching frequency (selectable) | 200 kHz, 500 kHz and 1 MHz |
Short-circuit proof/overload proof | Yes |
Output current limitation | Yes, automatic reactivation after short-circuit/overload |
Resistance to feedback against 24V signals | Yes |
Resistance to feedback against reverse polarity | Yes |
Max. cable length, shielded (depending on sensor) | Typ. 12.5 m @ 1MHz |
Parameter | Value |
---|---|
Number of channels | 1 |
Connection | Terminals 1.3, 1.4 |
Reference potential | Terminals 1.9, 4.9, 5.9, 6.9, 7.9 for M (0 V) |
Differential output voltage | ≥ 2.4 V at 10 mA |
Output delay (0->1 or 1->0) | Max. 0.35 µs |
Switching frequency (selectable) | 200 kHz, 500 kHz, 1 MHz |
Short-circuit proof/overload proof | Yes |
Output current limitation | Yes, automatic reactivation after short-circuit/overload |
Resistance to feedback against 24V signals | Yes |
Resistance to feedback against reverse polarity | Yes |
Max. cable length, shielded (depending on sensor) | 100 m |
Parameter | Value | ||
---|---|---|---|
Number of channels per module | 16 (synchronous sampled) | ||
Connection | Terminals 2.0…2.7, 5.0…5.1 for AI-, 3.0…3.7, 6.0…6.7 for AI+ | ||
Indication of the input signal | One bicolor LED per channel for signal and error messages. | ||
Measurement resolution | ≥ 23 Bit | ||
Resolution | 32 Bit external use | ||
Accurracy at +25 °C | ≤+/-0.1 % | ||
Accurracy over operating temperature and vibration | ≤+/-0.5 % | ||
Sample rate/bandwidth high (0 dB) | 50 kHz/20 kHz (min. -121 dB/22.5 kHz) 25 kHz/10 kHz (min. -116 dB/11.25kHz) 12.5 kHz/5 kHz (min. -116 dB/5.63 kHz) 6.25 kHz/2.5 kHz (min. -116 dB/2.81 kHz) 3.13 kHz/1.25 kHz (min. -116 dB/1.41 kHz) 1.56 kHz/0.625 kHz (min. -116 dB/0.70 kHz) 0.78 kHz/0.312 kHz (min. -120 dB/0.36 kHz) 0.39 kHz/0.156 kHz (min. -121 dB/0.18 kHz) 0.20 kHz/0.080 kHz (min. -121 dB/0.09 kHz) 0.10 kHz/0.040 kHz (min. -130 dB/0.05 kHz) selectable per channel |
||
Data storage | 128 MB | ||
Measurement time | Selectable per channel | ||
Input type default setting | unused | ||
Input type (selectable per input) | IEPE | -10 V…+10 V | |
Bandwidth low | min. 3 dB/< 0.1 Hz | min. 3 dB/< 0.1 Hz or DC (selectable) | |
Dynamic range (SFDR) | > 100 dB | ||
SINAD (300 Hz/1 kHz sine, 50 k SPS) | |||
0 dB from full scale | < -90 dB | < -95 dB | |
-20 dB from full scale | < -75 dB | < -80 dB | |
-40 dB from full scale | < -55 dB | < -60 dB | |
Input range | +2 V…+18 V | -10 V…+10 V | |
Measurement range | +/- 6 V (DC coupled) | -10 V…+10 V | |
Input DC bias range, common mode range | +8 V…+12 V | +/-1 V | |
Current source per channel | Typ. 4.2 mA (+/- 7 % over temperature) | - | |
Input resistance AI- to M | Typ. 27 Ohm (PTC) | ||
Channel input impedance (AI+/AI-) | |||
< 1 kHz | > 1 MOhm | > 2 MOhm | |
5 kHz | > 100 kOhm | > 40 kOhm | |
10 kHz | > 60 kOhm | > 25 kOhm | |
20 kHz | > 40 kOhm | > 8 kOhm | |
Error detection | Short circuit, open wire | - | |
Max. cable length, shielded (depending on sensor) | 100 m |