Technical Data of the InterfacesΒΆ

Interface standards

The serial interfaces RCOM and OPERATOR are designed according to the standards EIA RS-232 and EIA RS-485. Both interfaces can be operated in RS-232 or in RS-485 mode.

Technical data

Serial interface standard EIA RS-232 or EIA RS-485
Interface connector Pluggable 9-pole terminal block
Potential separation Yes, from the CPU, 500 V DC
Serial interface parameters Protocol interface configurable via PLC configuration. Preset configuration for debugging the terminal interface.
Modes of operation Data exchange
Protocols supported RCOM/RCOM+

The pin assignment of the serial interfaces RCOM and OPERATOR is identical to the serial interface COM1 of the AC500 CPUs PM57x, PM58x and PM59x.