Comparison CI581 and CI582¶
Technical data of CI581 and CI582
Interface | CAN | |
Protocol | CANopen® | |
Power supply | From the process supply voltage UP | |
Supply of the electronic circuitry of the I/O expansion modules attached | Through the expansion bus interface (I/O-Bus) | |
Rotary switches | For setting the CANopen® Node ID for configuration purposes (00h to FFh) | |
LED displays | For system displays, signal statuses, errors and power supply | |
External supply voltage | Via terminals ZP, UP and UP3 (process supply voltage 24 V DC) | |
Transmission rates | 10 / 20 / 50 / 125 / 250 / 500 / 800 kbit/s 1 Mbit/s Auto baudrate detection is supported | |
Bus connection | Depending on used Terminal unit TU510: 9-pole Sub-D connector TU518: 10-pole terminal block | |
Processor | Hilscher netX100 | |
Expandability | Max. 10 S500 I/O modules | |
Status display | Module status: PWR/RUN, CN-RUN, CN-ERR, E-ERR, I/O-Bus | |
Adjusting elements | 2 rotary switches for generation of the node address | |
Ambient temperature | System data AC500 System Data AC500 System data AC500 XC System Data AC500-XC |
|
Current consumption | UP: 0,2 A UP3: 0,06 A + 0,5 A max. per output | |
Weight (without Terminal Unit) | Ca. 125g | |
Process supply voltages UP/UP3 | ||
Rated value | 24 V DC (for inputs and outputs) | |
Max. load for the terminals | 10 A | |
Protection against reversed voltage | Yes | |
Rated protection fuse on UP/UP3 | 10 A fast | |
Electrical isolation | CANopen® interface against the rest of the module | |
Inrush current from UP (at power up) | On request | |
Current consumption via UP (normal operation) | 0.2 A | |
Current consumption via UP3 | 0.06 A + 0.5 A max. per output | |
Connections | Terminals 2.8 and 3.8 for +24 V (UP) Terminal 4.8 for +24 V (UP3) Terminals 2.9, 3.9 and 4.9 for 0 V (ZP) |
|
Max. power dissipation within the module | 6 W | |
Reference potential for all digital inputs and outputs | Minus pole of the supply voltage, signal name ZP | |
Setting of the CANopen® Node ID identifier | With 2 rotary switches at the front side of the module | |
Mounting position | Horizontal Or vertical with derating (output load reduced to 50 % at 40 °C per group) |
|
Cooling | The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet. |
Note
All I/O channels (digital and analog) are protected against reverse polarity, reverse supply, short circuit and continuous overvoltage up to 30 V DC.
The difference of those devices can be found in their input and output characteristics.
Input/Output Characteristics of CI581-CN
Inputs and outputs | 8 digital inputs (24 V DC; delay time configurable via software) 8 digital transistor outputs (24 V DC, 0.5 A max.) 4 analog inputs, configurable as:
2 analog outputs, configurable as:
|
Resolution of the analog channels | 12 bits |
Fast counter | Integrated, configurable operating modes |
Input/Output Characteristics of CI582-CN
Inputs and outputs | 8 digital inputs (24 V DC) 8 digital transistor outputs (24 V DC, 0.5 A max.) 8 configurable digital inputs/outputs (24 V DC, 0.5 A max.) |