Technical Data PDP21, PDP22

Supply voltage 24 V DC +30 % / -20 % (19.2…31.2 V DC)
Safety insulation PELV according to EN 60950
Current consumption  
- at 19.2 V 46 mA
- at 24.0 V 37 mA
- at 31.2 V 31 mA
Mounting on the terminal device, fixed with a screw (provided on delivery) or by M12 box nut fixing
Power line failure bridging time, to be performed by the power supply unit min. 10 ms
Recommended power supply unit Type: CP-24/5.0 adj.
  Order number: 1 SVR 423 416 R0100
  can be adjusted to max. 28 V DC
Bus termination active bus-line terminator 150 Ω at both ends of the bus, the bus master units (or repeaters) often offer a bus-line terminator at the beginning of the bus line
Modes of data communication between FieldBusPlug and device parallel and serial
Scope of data according to PROFIBUSâ DP specifications
Construction of the FieldBusPlug cable round cable, black, 2 x 0.34 mm² for supply voltage, 2 x 0.25 mm² for data lines, 2 connected shields
PDP21, PDP22 pin assignment

1 +24 V DC (brown)

2 Bus-N = A (green)

3 0 V DC (blue)

4 BUS-P = B (rot)

5 Shield (bare)

../_images/a9785b596c196dc00a33139074764b39
Warning: Exchange of bus signal lines with supply lines can cause destruction of the plug.
Load capacity of plugs and cables max. 4 A
Degree of protection IP 65, if M12 box nut fixing is used at the terminal device (e.g. sensor), IP 20, if mounting is performed using the supplied fastening screw (e.g. for UMC22-FBP)
Ambient temperature  
- storage -20°C…+70°C
- operation 0…+55°C
Dimensions see
Total power dissipation PDP21, PDP22 max. 0.9 W

Weight

- plug with cable 0.25 m

- plug with cable 0.5 m

- plug with cable 1.0 m

- plug with cable 5.0 m

0.09 kg

0.10 kg

0.13 kg

0.35 kg

Bus address setting

- with address switches or similar on the terminal device

- with addressing set CAS21-FBP

Address range

1 to 126, recommended 3 to 125,

0 to 2 and 126 to 128 are reserved for particular tasks

Diagnosis with LEDs see PDP21, PDP22 description “Indicators on the front panel”