LED Status¶
PROFIBUS® status |
Device status | Status / cause | ||
---|---|---|---|---|
LED green H1 |
LED red H2 |
LED green H3 |
LED red H4 |
|
off | off | off | off | Power supply is missing |
on | flashes | Possible errors: - No connection to the bus master, e.g. PROFIBUSâ is not operating - The PDP21/PDP22 has a slave address that is not configured in the bus master - Parameter length and slave address are correct but the I/O configuration of the slave does not meet the configuration sent by the bus master |
||
flashes | on | The device parameters received from the bus master are formal incorrect, e.g. of other length | ||
off | on | Connection to the bus master is interrupted longer than the timeout set by the bus master before interruption | ||
on | off | Normal data exchange to the PROFIBUSâ DP master | ||
on | off | Normal data exchange to the terminal device | ||
flashes | flashes | flashes | flashes | Plug is under self-test during power-up |
flashes | off | Plug is waiting for configuration data to be sent from the device (number of input/output bytes, number of parameter bytes, internal baud rate etc.) Note: If no data has been sent by the terminal device within 3 s, the plug switches to the parallel mode. |
||
off | flashes | Error: can be remedied, e.g. connection to the terminal device is broken | ||
off | on | Error: cannot be remedied, e.g. incorrect check sum in the Flash. Exchange the plug. |