LED Status

PROFIBUS®

status

Device status Status / cause

LED

green

H1

LED

red

H2

LED

green

H3

LED

red

H4

 
off off off off Power supply is missing
on flashes    

Possible errors:

- No connection to the bus master, e.g. PROFIBUSâ is not operating

- The PDP21/PDP22 has a slave address that is not configured in the bus master

- Parameter length and slave address are correct but the I/O configuration of the slave does not meet the configuration sent by the bus master

flashes on     The device parameters received from the bus master are formal incorrect, e.g. of other length
off on     Connection to the bus master is interrupted longer than the timeout set by the bus master before interruption
on off     Normal data exchange to the PROFIBUSâ DP master
    on off Normal data exchange to the terminal device
flashes flashes flashes flashes Plug is under self-test during power-up
    flashes off

Plug is waiting for configuration data to be sent from the device (number of input/output bytes, number of parameter bytes, internal baud rate etc.)

Note: If no data has been sent by the terminal device within 3 s, the plug switches to the parallel mode.

    off flashes Error: can be remedied, e.g. connection to the terminal device is broken
    off on Error: cannot be remedied, e.g. incorrect check sum in the Flash. Exchange the plug.