Unipolar Voltage Input Range, \ Measuring Bridge, Digital Input¶
| Range | 0 … +5 V | 0 … +10 V | Digital input | Digital value | |
|---|---|---|---|---|---|
| decimal | hex. | ||||
| Overflow | > 5.8794 | > 11.7589 | 32767 | 7FFF | |
| Measured value too high | 5.8794 : 5.0002  | 
11.7589 : 10.0004  | 
32511 : 27649  | 
7EFF : 6C01  | 
|
Normal range  | 
5.0000 : 0.0002  | 
10.0000 : 0.0004  | 
ON | 27648 : 1  | 
6C00 : 0001  | 
| 0.0000 | 0.0000 | OFF | 0 | 0000 | |
| Measured value too low | -0.0002 : -0.8794  | 
-0.0004 : -1.1759  | 
-1 : -4864  | 
FFFF : ED00  | 
|
| Underflow | < -0.8794 | < -1.7589 | -32768 | 8000 | |