Technical Data¶
The System Data of AC500 and S500 System Data AC500 are valid for standard version.
The System Data AC500-XC are valid for the XC version.
Only additional details are therefore documented below.
Process voltage | |||
Connections | Terminals 1.8, 2.8, 3.8 and 4.8 for +24 V (UP) as well as 1.9, 2.9, 3.9 and 4.9 for 0 V (ZP) | ||
Rated value | 24 V DC | ||
Max. ripple | 5 % | ||
Protection against reversed voltage | Yes | ||
Rated protection fuse on UP | 10 A fast | ||
Electrical isolation | Yes, per module | ||
Current consumption | |||
From 24 V DC power supply at the terminals UP/L+ and ZP/M of the CPU/Bus Module | Ca. 2 mA | ||
Current consumption from UP in normal operation | 130 mA | ||
Inrush current from UP (at power up) | On request | ||
Max. length of analog cables, conductor cross section > 0.14 mm² | 100 m | ||
Conversion error of the analog values caused by non-linearity, adjustment error at factory and resolution within the normal range | Typ. | 0.1 % (voltage) 0.3 % (current, resistor) For XC version below 0 °C and above 60 °C: on request |
|
Max. | 0.7 % (voltage) 0.9 % (current, resistor) 0.5 % (thermocouple) 1.0 K (resistance temperature detectors) For XC version below 0 °C and above 60 °C: on request |
||
Weight | 130 g | ||
Mounting position | Horizontal or vertical with derating (max. temperature 40 °C) |
||
Cooling | The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet. |
Note
All I/O channels (digital and analog) are protected against reverse polarity, reverse supply, short circuit and continuous overvoltage up to 30 V DC.