Technical Data

The System Data of AC500 and S500 System Data AC500 are valid for standard version.

The System Data AC500-XC are valid for the XC version.

Only additional details are therefore documented below.

Process voltage  
  Connections Terminals 1.8, 2.8, 3.8 and 4.8 for +24 V (UP) as well as 1.9, 2.9, 3.9 and 4.9 for 0 V (ZP)
  Rated value 24 V DC
  Max. ripple 5 %
  Protection against reversed voltage Yes
  Rated protection fuse on UP 10 A fast
  Electrical isolation Yes, per module
Current consumption  
  From 24 V DC power supply at the terminals UP/L+ and ZP/M of the CPU/Bus Module Ca. 2 mA
  Current consumption from UP in normal operation 130 mA
  Inrush current from UP (at power up) On request
Max. length of analog cables, conductor cross section > 0.14 mm² 100 m
Conversion error of the analog values caused by non-linearity, adjustment error at factory and resolution within the normal range Typ.

0.1 % (voltage)

0.3 % (current, resistor)

For XC version below 0 °C and above 60 °C: on request

Max.

0.7 % (voltage)

0.9 % (current, resistor)

0.5 % (thermocouple)

1.0 K (resistance temperature detectors)

For XC version below 0 °C and above 60 °C: on request

Weight 130 g
Mounting position

Horizontal

or vertical with derating (max. temperature 40 °C)

Cooling The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet.

Note

All I/O channels (digital and analog) are protected against reverse polarity, reverse supply, short circuit and continuous overvoltage up to 30 V DC.