Parameterization¶
The arrangement of the parameter data is depending on the firmware version installed inside the CPUs and Bus Modules:
| Firmware version | Mounting position | Configuration | 
|---|---|---|
| Firmware version < V2.0.0 | 
 | The arrangement of the parameter data is performed by PLC-Configuration inside Control Builder software. | 
| 
 | The arrangement of the parameter data is performed by your master configuration software SYCON.net in connection with the S500 GSD files and in conjunction with the Control Builder software. | |
| Firmware version > V2.0.0 | 
 | The arrangement of the parameter data is performed by Control Builder Plus software. | 
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configuration.
Module AI531: Module slot address: Y = 1 … 7
| No. | Name | Value | Internal value | Internal value, Type | Default | Min. | Max. | EDS Slot/Index | 
|---|---|---|---|---|---|---|---|---|
| 1 | Module ID | Internal | 1535 *1) | Word | 1535 0x05ff | 0 | 65535 | 0x0Y01 | 
| 2 *2) | Ignore module | No Yes | 0 1 | Byte | No 0x00 | not for FBP | ||
| 3 | Parameter length in bytes | Internal | 36 | Byte | 36 | 0 | 255 | 0x0Y02 | 
| 4 | Check supply | Off On | 0 1 | Byte | On 0x01 | 0x0Y03 | ||
| 5 | Analog data format | Default | 0 | Byte | Default 0x00 | 0x0Y04 | 
*1) With CS31 and addresses less than 70 and FBP, the value is increased by 1
*2) Not with FBP
Input channel (8x)
| No. | Name | Value | Internal value | Internal value, Type | Default | Min. | Max. | EDS Slot Index | 
|---|---|---|---|---|---|---|---|---|
| 1 | Channel configuration | see below *3) | see below *3) | Byte | 0x00 see below *4) | 0x0Y07 | ||
| 2 | Channel monitoring | see below *5) | see below *5) | Byte | 0x03 see below *6) | |||
| 3 | Line frequency suppression | see below *7) | see below *7) | Byte | 0x00 see below *8) | |||
| 4 | Compensation channel | see below *9) | see below *9) | Byte | 0x00 see below *10) | 
| *3) | Internal value | Operating modes for the analog inputs, individually configurable | 
|---|---|---|
| *4) | 0 | Unused (default) | 
| 2 | Digital input | |
| 34 | Analog input -50 mV … +50 mV | |
| 35 | Analog input -500 mV … +500 mV | |
| 36 | Analog input -1 V … +1 V | |
| 7 | Analog input -5 V … +5 V | |
| 5 | Analog input -10 V … +10 V | |
| 6 | Analog input 0 V … +5 V | |
| 1 | Analog input 0 V … +10 V | |
| 37 | Analog input -20 mA … +20 mA | |
| 3 | Analog input 0 mA … 20 mA | |
| 4 | Analog input 4 mA … 20 mA | |
| 14 | Analog input Pt100 (2-wire), -50 °C … +70 °C | |
| 15 | Analog input Pt100 (3-wire), -50 °C … +70 °C | |
| 48 | Analog input Pt100 (4-wire), -50 °C … +70 °C | |
| 57 | Analog input Pt100 (2-wire), -50 °C … +70 °C (resolution: 0,01 K) | |
| 58 | Analog input Pt100 (3-wire), -50 °C … +70 °C (resolution: 0,01 K) | |
| 59 | Analog input Pt100 (4-wire), -50 °C … +70 °C (resolution: 0,01 K) | |
| 8 | Analog input Pt100 (2-wire), -50 °C … +400 °C | |
| 9 | Analog input Pt100 (3-wire), -50 °C … +400 °C | |
| 49 | Analog input Pt100 (4-wire), -50 °C … +400 °C | |
| 45 | Analog input Pt100 (2-wire), -200 °C … +850 °C | |
| 46 | Analog input Pt100 (3-wire), -200 °C … +850 °C | |
| 47 | Analog input Pt100 (4-wire), -200 °C … +850 °C | |
| 16 | Analog input Pt1000 (2-wire), -50 °C … +400 °C | |
| 17 | Analog input Pt1000 (3-wire), -50 °C … +400 °C | |
| 50 | Analog input Pt1000 (4-wire), -50 °C … +400 °C | |
| 18 | Analog input Ni1000 (2-wire), -50 °C … +150 °C | |
| 19 | Analog input Ni1000 (3-wire), -50 °C … +150 °C | |
| 51 | Analog input Ni1000 (4-wire), -50 °C … +150 °C | |
| 39 | Analog input Cu50 1.426 (2-wire) -50 °C … +200 °C | |
| 40 | Analog input Cu50 1.426 (3-wire) -50 °C … +200 °C | |
| 41 | Analog input Cu50 1.426 (4-wire) -50 °C … +200 °C | |
| 42 | Analog input Cu50 1.428 (2-wire) -200 °C … +200 °C | |
| 43 | Analog input Cu50 1.428 (3-wire) -200 °C … +200 °C | |
| 44 | Analog input Cu50 1.428 (4-wire) -200 °C … +200 °C | |
| 24 | Analog input J-type thermocouple -210 °C … +1200 °C | |
| 25 | Analog input K-type thermocouple -270 °C … +1372 °C | |
| 30 | Analog input N-type thermocouple -270 °C … +1300 °C | |
| 27 | Analog input S-type thermocouple -50 °C … +1768 °C | |
| 28 | Analog input T-type thermocouple -270 °C … +400 °C | |
| 38 | Analog input resistor 50 kW | |
| 52 | Temperature-internal reference point | |
| 53 | Common Mode Voltage | 
Channel monitoring
| *5) | Internal value | Monitoring | 
|---|---|---|
| *6) | 0 | Plausibility, open-circuit (cut wire) and short-circuit (default) | 
| 3 | No monitoring | 
Line frequency suppression
| *7) | Internal value | Line frequency suppression | 
|---|---|---|
| *8) | 0 | 50 Hz | 
| 1 | 60 Hz | |
| 2 | No line frequency suppression | 
Compensation channel
| *9) | Internal value | Compensation channel | 
|---|---|---|
| *10) | 0 | Internal compensation (default) | 
| 1 | Channel 0 (possible with channels 1, 2, 3) | |
| 2 | Channel 1 (possible with channels 0, 2, 3) | |
| 3 | Channel 2 (possible with channels 0, 1, 3) | |
| 4 | Channel 3 (possible with channels 0, 1, 2) | |
| 5 | Channel 4 (possible with channels 5, 6, 7) | |
| 6 | Channel 5 (possible with channels 4, 6, 7) | |
| 7 | Channel 6 (possible with channels 4, 5, 7) | |
| 8 | Channel 7 (possible with channels 4, 5, 6) | |
| 9 | External with temperature definition | 
GSD file:
| AI531 | Ext_User_Prm_Data_Len = Ext_User_Prm_Data_Const(0) = | 39 0x05, 0xff, 0x24, \ 0x01, 0x00, 0x00, 0x00 \ 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, \ 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, \ 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, \ 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00; | 