Functionality

8 analog inputs, individually configurable for unused (default setting)
0 … 5 V, 0 … 10 V
-50 … +50 mV, -500 … +500 mV
-1 … +1 V, -5 … +5 V, -10 V … +10 V
0 … 20 mA
4 … 20 mA
-20 … 20 mA
Pt100 -50 °C … +70 °C bzw. 400 °C (2-, 3- and 4-wire)
Pt100 -200 °C … +850 °C (2-, 3- and 4-wire)
Pt1000 -50 °C … +400 °C (2-, 3- and 4-wire)
Ni1000 -50 °C … +150 °C (2-, 3- and 4-wire)
Cu50 (1.426) -50 °C … +200 °C (2-, 3- and 4-wire)
Cu50 (1.428) -200 °C … +200 °C (2-, 3- and 4-wire)
0 … 50 kOhm
Thermocouples of types J, K, T, N, S
Resistance measuring bridge
digital signals (digital input)
Resolution of the analog channels  
Voltage and current, bipolar 15 bits plus sign
Voltage and current, unipolar 15 bits
Temperature 0.1 °C (0,01°C at Pt100 -50 °C … +70 °C)
   
LED displays 11 LEDs for signals and error messages
Internal power supply through the expansion bus interface (I/O-Bus)
External power supply via terminals (process voltage UP = 24 V DC)