Connection of passive-type analog sensors (current) and series-connection \ of an additional analog sensor

The following figure shows the connection of passive-type analog sensors (current) and series-connection of an additional analog sensor.

../_images/5c7235e85c7a54550a33139012d207d61

Connection of passive-type analog sensors (current) and series-connection of an additional analog sensor. 1 analog sensor requires 1 channel.

Note

If series-connection of an additional input is used, it must be kept in mind that the input resistance of the AI531 (ca. 330 Ω) must be added to the input resistance of the second device. Make sure that the maximum permitted load resistance of the analog sensor is not exceeded (see the data sheet of the analog sensor).

Note

The input of the AI531 is not related to ZP. If the input of the second device is related to ZP, the order of sequence in the series-connection must be observed by all means (from the sensor to the AI531 and then to the input of the second device).

The following measuring ranges can be configured AI531 Analog Input Module AI531 Analog Input Module:

Current -20 … 20 mA* 1 channel used
Current 0 … 20 mA* 1 channel used
Current 4 … 20 mA 1 channel used

* This setting is not applicable with passive-type analog sensors (current).

The function of the LEDs is described under Diagnosis and displays / displays AI531 Analog Input Module.

Unused input channels can be left open, because they are of low resistance.