Connection of passive-type analog sensors (current)¶
The following figure shows the connection of passive-type analog sensors (current).
Connection of passive-type analog sensors (current). 1 analog sensor requires 1 channel.
The following measuring ranges can be configured AI531 Analog Input Module AI531 Analog Input Module:
Current | -20 … 20 mA* | 1 channel used |
Current | 0 … 20 mA* | 1 channel used |
Current | 4 … 20 mA | 1 channel used |
* This setting is not applicable with passive-type analog sensors (current).
The function of the LEDs is described under Diagnosis and displays / displays AI531 Analog Input Module.
Unused input channels can be left open, because they are of low resistance.