Input Description

../_images/828593b2e38ae4d80a33139000eba54e

EN

Data_Type Default_Value Range Unit
BOOL - - -

If a FALSE->TRUE edge is applied to input EN, all further inputs are read in. If the input values are valid, a corresponding request message is sent to the Communication Module. While this request message is processed, output DONE is set to FALSE. If at least one input value is invalid, an error is indicated at output ERR. Additionally, the termination of the request processing is indicated by DONE = TRUE. While the request is processed, state changes at input EN are recognized but not evaluated.

SLOT

Data_Type Default_Value Range Unit
BYTE - 1 - 4 -

The SLOT input selects the Communication Module serving the PROFINET:sup:® IO-Device described by DEV_NAME. Valid values are 1…4, counting from right to left, starting with 1 as the first Communication Module left to the CPU.

For PM595 Processor Modules, internal PROFINET Communication Module with connector ETH3 is slot 5, ETH4 is slot 6.