Technical Data

The System Data of AC500 and S500 System Data AC500are valid for standard version.

The System Data of AC500-XC System Data AC500-XCare valid for the XC version.

Only additional details are therefore documented below.

General data of the Processor Modules

For more information, please refer to the AC500 System Data System Data AC500chapter.

Connection of the supply voltage 24 V DC at the removable terminal block of the Processor Module at a 5-pole removable terminal block with spring connection
  Current consumption from 24 V DC 0.4 A
  Inrush current at 24 V DC 1 A²s *)
  Max. power dissipation within the module 15 W
  Slots for Communication Modules 2
  Processing Module’s interfaces I/O-Bus, COM1, COM2
  Processing Module’s network interfaces

ETH1 and ETH2 for Ethernet-based system communication

ETH3.1 and ETH3.2 for Ethernet-based fieldbusses with switch functionality

ETH4.1 and ETH4.2 for Ethernet-based fieldbusses with switch functionality

Connection system see System Assembly chapter AC500 (Standard)
Dimensions see System Assembly chapter Mechanical Dimensions AC500
  Width x height x depth 230 x 152 x 87 mm
  Weight 1070 g
  Mounting position horizontal or vertical with derating (50 % output load, reduction of temperature to 40 °C)

*1) The melting integral for the Processor Module is depending on the integrated Processing Module power supply, number and type of Communication Modules and I/O modules connected to the I/O-Bus.

Detailed data

Parameter Value
Flash memory for boot projects, symbols and web pages 32768 kB
SDRAM for user program 16384 kB
SDRAM for user data 16384 kB
Expandable memory None
Integrated mass storage memory 4 GB non rotating flashdisk
Pluggable SD Memory Card for: x
  User data storage
  Program source code storage
  Firmware update
Cycle time for 1 instruction  
  Binary Min. 0.0006 µs
  Word Min. 0.001 µs
  Floating point Min. 0.001 µs
Max. number of central inputs and outputs (10 exp. modules):  
  Digital inputs 320
  Digital outputs 240
  Analog inputs 160
  Analog outputs 160
Number of decentralized inputs and outputs Depends on the used field bus (as an info on the CS31 Bus: up to 31 stations with up to 120 DI / 120 DO each)
Data backup

Battery for PM595-4ETH-F,

MRAM for PM595-4ETH-M-XC without battery

Data buffering time at 25 °C About 3 years
Battery low indication Warning indication issued about 2 weeks before the battery charge becomes critical
Real-time clock  
  With battery back-up x
  Accuracy Typ. ± 2 s / day at 25 °C

Integrated Communication Module,

ETH = Ethernet RJ45

2x Ethernet,

2x Ethernet interfaces with downloadable protocol e.g. PROFINET IO,

ETherCAT (in preparation)

Number of external Communication Modules Up to 2 Communication Modules like PROFIBUS® DP, Ethernet, CANopen® or Safety Module SM560-S. There is no restriction concerning the Communication Module types and Communication Module combinations (e.g. up to 2 PROFIBUS® DP Communication Modules are possible)
LEDs 5 to display statuses, rest of LEDs reserved
LCD display Optional
Buttons and switches

1 button for Reset (Reserved)

1 Button (Reserved)

1 Switch for RUN/STOP

Certifications CE, GL, DNV, BV, RINA, LRS, cUL

Ordering Data

Order No. Scope of Delivery
1SAP 155 500 R0279 PM595-4ETH-F Processor Module, User Progr./Data memory 16 MB / 16 MB, 1.3 GHz, 24 V DC, Memory Card Slot, interfaces 2x RS232-485, 2x independent Ethernet interfaces (Progr., Webserver, IEC60870-5-104 protocol), 2x independent Ethernet based interfaces with 2-port switch (for downloadable fieldbus protocols e.g. PROFINET IO)
1SAP 351 500 R0279 PM595-4ETH-M-XC Processor Module, User Progr./Data memory 16 MB / 16 MB, 1.0 GHz, 24 V DC, Memory Card Slot, interfaces 2x RS232-485, 2x independent Ethernet interfaces (Progr., Webserver, IEC60870-5-104 protocol), 2x independent Ethernet based interfaces with 2-port switch (for downloadable fieldbus protocols e.g. PROFINET IO) for extreme condition environments
Order No. Scope of Delivery
Accessories
1SAP 182 700 R0001 TA541 Lithium Battery
1SAP 180 100 R0001 MC502, SD Memory Card
1SAP 180 200 R0001 TK501, Programming cable SUB-D / SUB-D, length: 5 m
1SAP 180 200 R0101 TK502, Programming cable terminal block / SUB-D, length: 5 m
1TNE 968 901 R1100 TK503, Programming cable USB / SUB-D (RS-485), length 3 m
1SAP 182 300 R0001 TA535 Protective Caps for XC Devices
1SAP 182 600 R0001 TA540, Front cover as spare part (3 pieces)
1SAP 182 800 R0001 TA543, Screw mounting accessory (20 pieces)