Parameters of the Module

Name Value

Internal

Value

Internal

Value, type

Default
Module ID *1) Internal 7010 WORD 7010
Parameter length Internal 33 BYTE 33
Error LED / Failsafe function *2) On 0 BYTE 0
Off by E4 1
Off by E3 3
On + failsafe 16
Off by E4 + failsafe 17
Off by E3 + failsafe 19

*1) With a faulty ID, the module reports a “parameter error” and does not perform cyclic process data transmission

*2) Setting Meaning
  On Error-LED lights up at errors of all error classes, Failsafe-mode off
  Off by E4 Error LED lights up at errors of error classes E1, E2 and E3, Failsafe-mode off
  Off by E3 Error LED lights up at errors of error classes E1 and E2, Failsafe-mode off
  On + Failsafe Error-LED lights up at errors of all error classes, Failsafe-mode on*
  Off by E4 + Failsafe Error LED lights up at errors of error classes E1, E2 and E3, Failsafe-mode on*
  Off by E3 + Failsafe Error LED lights up at errors of error classes E1 and E2, Failsafe-mode on*

All values are validated during the parameterization of the CI504-PNIO according to the appended expansion modules. In the case of error, a diagnostic message “parameter errors” is generated and the cyclic process data transfer is terminated.