Planning example for CM574-RS/CS31 busΒΆ
Planning the cyclic data exchange of the inputs and outputs of the CS31 bus modules on the CM574-RS with a Processor Module is illustrated in the following example configuration:
- PM582 with CM574-RS in slot 1
- CM574-RS: COM1 CS31 bus, COM2 online access
- CS31 cluster 1: DC551 with HW address switch = 70, i.e. address 0 and fast counter enabled
- CS31 cluster 2: DC551 with HW address switch = 1 and S500 extensions 1xAX522 + 1xDC532
Accordingly, PLC configuration in the CM574-RS project is as follows:
If you open the last module (here: DC532), you can see that the highest input byte is %IB1037, and the highest output byte is %QB1041.
Thus, the configuration on the CS31 bus has
38 bytes for inputs and 42 bytes for outputs.