Technical Data of the Digital \ Outputs
Number of channels per module |
8 |
Distribution of the channels into groups |
1 group of 8 channels |
Terminals of the channels DO0 to DO7 |
Terminals 4.0 to 4.7 |
Reference potential for all outputs |
Terminals 2.9 … 4.9 (minus pole of the supply voltage, signal name ZP) |
Common power supply voltage |
For all outputs terminal 4.8 (plus pole of the supply voltage, signal name UP3) |
Output voltage for signal 1 |
UP3 (-0.8 V) |
Output delay (0->1 or 1->0) |
On request |
Output current |
|
Rated value per channel |
500 mA @ UP3 = 24 V |
Max. value (all channels together) |
4 A |
Leakage current with signal 0 |
< 0.5 mA |
Fuse for UP3 |
10 A fast |
Demagnetization with inductive DC load |
Via internal varistors (see figure below this table) |
Output switching frequency |
|
With resistive load |
On request |
With inductive loads |
Max. 0.5 Hz |
With lamp loads |
11 Hz max. @ 5 W max. |
Short-circuit proof / overload proof |
Yes |
Overload message (I > 0.7 A) |
Yes, after ca. 100 ms |
Output current limitation |
Yes, automatic reactivation after short-circuit/overload |
Resistance to feedback against 24V signals |
Yes (software-controlled supervision) |
Max. cable length |
|
Shielded |
1000 m |
Unshielded |
600 m |
The following drawing shows the circuitry of a digital input/output with the varistors for demagnetization when inductive loads are switched off.
1 |
Digital Output |
2 |
Varistors for demagnetization when inductive loads are turned off |