Addressing

A detailed description concerning addressing can be found in documentation of ABB Control Builder Plus Software.

Note

The CANopen® Bus Module CI582-CN reads the position of the rotary switches only during power-up, i. e. changes of the switch position during operation will have no effect until the next module initialization.

The range of permitted CANopen® Slave addresses is 1 to 127. Pay attention that the setting of an higher address (> 128) does not lead to an error response, but results in a special mode (DS401). In this special mode the device creates the node address by subtraction the value 128 from the address switches value.