Electrical Connection

The electrical connection is carried out using the terminals of the TF5x1_CMS.

Note

Mounting, disassembling and electrical connection for the Terminal Function Block and the I/O Modules are described in the S500 system data chapters Hardware S500.

The serial I/O bus is described in the S500 system data chapter 47413a605a2881ea0a317d3168fd2998.

Terminal assignment of the TF5x1_CMS

../_images/856aea4d75442cb20a317d310cb2338d1
Terminal Signal Meaning
1.0 FE Functional earth for encoder shield connection
1.1 A+ Input signal A of encoder 0
1.2 A- Inverted input signal A of encoder 0
1.3 B+ Input signal B of encoder 0
1.4 B- Inverted input signal B of encoder 0
1.5 Z+ Input signal Z of encoder 0
1.6 Z- Inverted input signal Z of encoder 0
1.7 5 V +5 V DC power supply output for encoder
1.8 L+ Process voltage L+ (24 V DC)
1.9 M Process voltage M (0 V DC)
2.0…2.7 AI0-…AI7- Negative input signal AI0…AI7 for analog channel 0…7
2.8/2.9 DI0/DI1 Input signal I0/I1 (standard digital input)
3.0…3.7 AI0+…AI7+ Positive input signal AI0…AI7 for analog channel 0…7
3.8/3.9 DC2/DC3 Signal of configurable digital input/output C2/C3
4.0…4.7 SH Shield connection
4.8 L+ Process voltage L+ (24 V DC)
4.9 M Process voltage M (0 V DC)
5.0…5.7 AI8-…AI15- Negative input signal AI0AI7 for analog channel 8…15
5.8 L+ Process voltage L+ (24 V DC)
5.9 M Process voltage M (0 V DC)
6.0…6.7 AI8+…AI15+ Positive input signal AI0…AI7 for analog channel 8…15
6.8 L+ Process voltage L+ (24 V DC)
6.9 M Process voltage M (0 V DC)
7.0…7.7 SH Shield connection
7.8 L+ Process voltage L+ (24 V DC)
7.9 M Process voltage M (0 V DC)

Caution

:strong:Risk of damaging the PLC modules!

The PLC modules must not be removed when the plant is powered on.

Make sure that all voltage sources (supply and process voltage) are switched off before you are removing or replacing a module.

Note

Analog signals must be laid in shielded cables. The analog cable shield must be only connected on the module side (SH terminals) to avoid relaxation currents influencing the measuring results and for optimal robustness against external noise. The shield connection must be as short as possible (< 3 cm). The analog shield is capacitive coupled internally with functional earth (FE). Generally to avoid unacceptable potential differences between different parts of the installation, low-resistance equipotential bonding conductors must be laid .

Caution

:strong:Risk of damaging the Processor Module and the Terminal Base!

The Processor Module and its Terminal Base may be damaged by voltages larger than the range allowed.

Never connect supply and process voltages > 30 V DC.

Attention

:strong:Risk of damaging the Terminal Base and the \ power supply!

Power supply and Terminal Base can be damaged by short circuits.

Make sure that the clamps L+ and M which exist twice are not connected in a wrong way (e. g. +/- of power supply is connected to both L+/L+ or both M/M)

Attention

:strong:Risk of damaging the Terminal Base!

Clamp and Terminal Base can be damaged by too large currents.

Make sure that the current through the spring terminals never exceed 10 A.

../_images/af22ecff6430994c0a317d3100e701a91

Terminal assignment and electrical connection