Technical Data¶
The System Data AC500 are valid for standard version System Data AC500.
The System Data AC500 XC are valid for the XC version System Data AC500-XC.
Only additional details are therefore documented below.
Parameter | Value | |
---|---|---|
Connection of the supply voltage 24 V DC at the TF5x1_CMS | The terminals 1.8, 4.8…7.8, 1.9, 4.9…7.9, 4.0…4.7, 7.0…7.7 are electrically interconnected within the TF5x1_CMS. Terminals 1.8, 4.8…7.8: Process voltage L+ = +24 V DC Terminals 1.9, 4.9…7.9: Process voltage M = 0 V Terminals 4.0…4.7, 7.0…7.7: Analog shield clamps SH Terminal 1.0: FE shield clamp of encoder |
|
Rated voltage | 24 V DC | |
Max. permitted total current | 10 A (between terminals 1.8, 4.8…7.8 and 1.9, 4.9…7.9) | |
Slots | ||
TF501_CMS | 1 Function Module FM502_CMS, 1 processor module PM592_ETH, 0 Communication Modules | |
TF521_CMS | 1 Function Module FM502_CMS, 1 processor module PM592_ETH, 2 Communication Modules | |
Processor module interfaces | I/O bus, COM1 | |
Width x height x depth | TF501_CMS: 136 x 135 x 29 mm | |
TF521_CMS: 192 x 135 x 29 mm | ||
Weight | TF501_CMS: 350 g | |
TF521_CMS: 400 g | ||
Mounting position | Horizontal or vertical |
Parameter | Value |
---|---|
I/O bus | I/O interface for directly adding up to 10 Terminal Units |
Terminal Block | 70 clamps for I/O, shield and power supply connection |
COM1 | Serial interface, 9-pole SUB-D connector, female |
Network interface (type must be equal to the type of the used processor module) |
Ethernet RJ45 |