Technical Data¶
The System Data of AC500 and S500 System Data AC500are valid for standard version.
The System Data of AC500-XC System Data AC500-XCare valid for the XC version.
Only additional details are therefore documented below.
| Communication module CM572-DP | |
|---|---|
| Field bus | PROFIBUS® DP Master V0 / V1 |
| Transmission rate | 9.6 kBit/s to 12 MBit/s |
| Protocol | PROFIBUS® DP Master V0 /V1 |
| Field bus connector | D-SUB, 9-pole, female |
| Processor | EC1-160, 48 MHz |
| Usable CPUs | PM57x, PM58x, PM59x PM57x (-y), PM58x (-y) and PM59x (-y) |
| Usable Terminal Bases | All TB5xx TB51x-TB54x |
| Ingress Protection | IP20 |
| Communication module interface | Dual-port memory, 8 kB |
| Current consumption from 24 V DC power supply at the Terminal Base of the CPU | Typ. 50 mA |
| Internal power supply | Through the Communication Module interface of the Terminal Base |
| Internal power supply with |
|
| Internal RAM memory (EC1) | 256 kB |
| External RAM memory | - |
| External Flash memory | 512 kB (firmware) |
| Status display | PWR, RDY, RUN, STA, ERR |
| Weight | Ca. 150 g |
Technical Data of the Interface
| Interface socket | 9-pole, SUB-D socket |
| Transmission standard | EIA RS-485 acc. to EN 50170, potential-free |
| Transmission protocol | PROFIBUS® DP, 12 Mbaud max. |
| Transmission rate | Baudrate 9.6 kbit/s up to 12.000 kbit/s |
| Status indication | By 5 LEDs |
Number of subscribers (master/slave modules per bus segment) |
32 max. |
| Number of subscribers via repeaters | 126 max. |