ETH- Terminal Units TU507-ETH and TU508-ETH for PROFINET:sup:®- or EtherCAT® Bus Modules¶
- TU507-ETH, Ethernet Terminal Unit, screw-type terminals
- TU508-ETH, Ethernet Terminal Unit, spring terminals
- XC version for usage in extreme ambient conditions available (TU508-ETH only)
Ethernet Terminal Unit TU508-ETH, for PROFINET:sup:® or EtherCAT® Bus Modules
Elements of the Ethernet Terminal Units | |
---|---|
1 | I/O-Bus (10-pole female) to electrically connect the first I/O Terminal Unit |
2 | Plug (1x 50-pole and 2x 38-pole) to electrically connect the inserted PROFINET:sup:®- or EtherCAT® Bus Module |
3 | With a screwdriver, inserted in this place, the ETH Terminal Unit and the adjacent I/O Terminal Unit can be shoved from each other |
4 | 2 holes for wall mounting |
5 | 2 RJ45-Interfaces with indication LEDs for connection with the PROFINET:sup:® or EtherCAT® network |
6 | 30 screw-type or spring terminals for signals and power supply voltages (UP and UP3) |
7 | DIN rail |
Sign for XC version |
Screw-type terminals (TU507-ETH) | Spring terminals (TU508-ETH) | ||||
Conductor | Screwdriver | Conductor | Screwdriver (opens terminal) |
Figure: Types of terminals
The Ethernet Terminal Units TU507-ETH (with screw-type terminals) and TU508-ETH (with spring terminals) are specifically designed for use with AC500/S500 Ethernet Bus Modules (e. g. CI501-PNIO).
The Ethernet Bus Modules plug into the Ethernet Terminal Unit. When properly seated, they are secured with two mechanical locks. All the electrical connections are made through the Ethernet Terminal Unit, which allows removal and replacement of the Ethernet Bus Modules without disturbing the wiring at the Ethernet Terminal Unit.
Note
Note: Mounting, disassembling and electrical connection for the Terminal Units and the I/O modules are described in detail in Mounting and disassembling the Terminal Units and the I/O modules Mounting and Disassembling the Terminal Units and the I/O Modules.
The terminals 1.8 and 2.8 as well as 1.9, 2.9 and 3.9 are electrically interconnected within the Ethernet Terminal Unit and have always the same assignment, independent of the inserted Bus Module:
- Terminals 1.8 and 2.8: process supply voltage UP = +24 V DC
- Terminal 3.8: process supply voltage UP3 = +24 V DC
- Terminals 1.9, 2.9 and 3.9: process supply voltage ZP = 0 V
The assignment of the other terminals is dependent on the inserted PROFINET®- or EtherCAT® Bus Module (see Ethernet Bus Modules Overview).
For usage in extreme ambient conditions (e.g. wider temperature and humidity range), a special XC version of the device is available (TU508-ETH only).
Attention
:strong:Risk of corossion!
Unused D-SUB connectors may corrode if using XC Devices in salt mist environments.
Protect unused D-SUB connectors with TA535 Protective Caps for XC Devices Protective Caps TA535 for XC Devices.