Technical Data

The System Data of AC500 and S500 System Data AC500are valid here.

The System Data of AC500-XC System Data AC500-XC are valid for the XC version.

Only additional details are therefore documented below.

Process supply voltage UP  
Connections Terminals 1.8 for +24 V (UP) and 1.9 for 0 V (ZP)
Rated value 24 V DC
Max. ripple 5 %
Absolute limits at XC version Above 60 °C: 20 V DC … 30 V DC
Protection against reversed voltage Yes
Rated protection fuse on UP 10 A fast
Electrical isolation Yes, per module
Current consumption  
From 24 V DC power supply at the Terminal Base of the CPU 10 mA
Current consumption from UP at normal operation / with outputs 10 mA + 5 mA per input
Inrush current from UP (at power up) 0,002 A²s
Max. power dissipation within the module 6 W (outputs unloaded)
Max. power dissipation within the module On request
Weight (without terminal block) Ca. 125 g
Mounting position Horizontal or vertical with derating (output load reduced to 50 % at 40°C per group)
Cooling The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet.
Altitude > 2000 m: On request

Note

ll I/O channels (digital or analog) are protected against reverse polarity, reverse supply, short circuit and continuous overvoltage up to 30 V DC.