Technical Data¶
The System Data of AC500 and S500 System Data AC500are valid here.
The System Data of AC500-XC System Data AC500-XC are valid for the XC version.
Only additional details are therefore documented below.
| Process supply voltage UP | |
| Connections | Terminals 1.8 for +24 V (UP) and 1.9 for 0 V (ZP) |
| Rated value | 24 V DC |
| Max. ripple | 5 % |
| Absolute limits at XC version | Above 60 °C: 20 V DC … 30 V DC |
| Protection against reversed voltage | Yes |
| Rated protection fuse on UP | 10 A fast |
| Electrical isolation | Yes, per module |
| Current consumption | |
| From 24 V DC power supply at the Terminal Base of the CPU | 10 mA |
| Current consumption from UP at normal operation / with outputs | 10 mA + 5 mA per input |
| Inrush current from UP (at power up) | 0,002 A²s |
| Max. power dissipation within the module | 6 W (outputs unloaded) |
| Max. power dissipation within the module | On request |
| Weight (without terminal block) | Ca. 125 g |
| Mounting position | Horizontal or vertical with derating (output load reduced to 50 % at 40°C per group) |
| Cooling | The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet. |
| Altitude | > 2000 m: On request |
Note
ll I/O channels (digital or analog) are protected against reverse polarity, reverse supply, short circuit and continuous overvoltage up to 30 V DC.