Short Description

The Terminal Bases TB51x to TB54x are used as sockets for Processor Modules and Communication Modules. Up to 10 I/O Terminal Units for I/O expansion modules can be added to these Terminal Bases.

The Terminal Bases have slots for one Processor Module and for Communication Modules as well as terminals and interfaces for power supply, expansion and networking.

Number of slots:
Terminal Base TB51x TB52x TB54x
Slots for Processor Modules 1 1 1
Slots for Communication Modules 1 2 4

Warning

:strong:Risk of malfunctions and damages to persons!

Unused slots for Communication Modules are not protected against accidentally touch. Dust and Dirt may cause contact problems and malfunctions.

Unused slots for Communication Modules must be covered with Dummy Communication Modules (TA524 TA524 - Dummy Communication Module).

I/O-Bus connectors must not be touched during operation.

Terminal Base TB511- TB521- TB523-2ETH TB541-ETH
  ETH ARCNET ETH ARCNET
Connection  
I/O-Bus I/O interface for directly adding up to 10 I/O Terminal Units
Power supply 5-pole removable terminal block
COM1 serial interface, 9-pole removable terminal block
COM2 serial interface, 9-pole SUB-D connector (female) - serial interface, 9-pole SUB-D connector (female)
Network interface (type must be equal to the type of the used Processor Module)

Ethernet

RJ45

ARCNET

BNC

Ethernet

RJ45

ARCNET

BNC

2x Ethernet

RJ45

Ethernet

RJ45

FBP interface Fieldbus-neutral slave interface (M12, 5-pole, male, fastening with screw) - Fieldbus-neutral slave interface (M12, 5-pole, male, fastening with screw)

Note

PM57x-ETH, PM58x-ETH and PM59x-ETH with ordering No. 1SAPxxxxxxR0271 can only be used with Terminal Bases with ordering No. 1SAPxxxxxxR0270.

PM5xx-2ETH can only be used with TB5x3-2ETH Terminal Bases.

For usage in extreme ambient conditions (e.g. wider temperature and humidity range), a special XC version of the device is available.