Block Wise Read of Single Parameterization (Object 2710hex to 271Ahex)ΒΆ
For reading of single parameters a special sequence is needed:
- Writing of SDO to the corresponding object with data structure defined in Parameter Indexes of CI581-CN.
- This writing requests the parameter indexes that should be read.
- Reading of SDO of the corresponding object to get the read parameters.
- The delivered data uses the same structure as defined in Parameter Indexes of CI582-CN.
- If the reading of the data isnt finished the device will reject the read service with abort code 08000021hex
- If no writing has been send before reading the device will reject the read service with abort code 08000000hex