Using UDP Data Exchange¶
The UDP data exchange can be used to realize communication with AC31 Devices and is an optional module that can be added to the AC500 Ethernet Communication Module.
Right-click on the Communication Module and select Add device to open the Add Device dialog where the UDP data exchange module is listed:
Double-click on UDP_data_exchange (UDP data exchange) to open the UDP data exchange Configuration in the editor window:
The following parameters are available:
Parameter | Default | Value | Meaning |
---|---|---|---|
Size of receive buffer | 8192 | 1464…65535 | Size of the receive buffer in [Bytes]. The behaviour in case of a full buffer can be determined with parameter Behaviour on receive buffer overflow. |
Size of transmit buffer high prio | 4096 | 0…65535 | Size of the high priority transmit buffer in [Bytes]. |
Size of transmit buffer low prio | 4096 | 0…65535 | Size of the low priority transmit buffer in [Bytes]. |
Size of timeout buffer | 2048 | 0…65535 | Size of the timeout buffer in [Bytes]. |
Number of header data | 10 | 0…1464 | Number of bytes that are copied into the timeout buffer for timeout packages. |
Receive broadcast | Disable | Disable | Reception of broadcast packages is disabled. |
Enable | Reception of broadcast packages is enabled. | ||
Behaviour on receive buffer overflow | Overwrite | Overwrite | Incoming packages will overwrite the oldest packages in case of a full receive buffer. |
Reject | Incoming packages will be rejected in case of a full receive buffer. | ||
UDP Port | 0 | 0…65535 | Port used for the UDP connection. See note below for further information. |
Note
The following ports are reserved and will cause a configuration error if selected: 1200, 1201, 123, 80, 24576, 25383.
At this operating mode, the Function Blocks have no input for setting a port, so the port has to be identically at both sides. Otherwise, a communication is not possible.