Parameterization

The arrangement of the parameter data is performed with Control Builder Plus software.

The parameter data directly influences the functionality of modules.

For non-standard applications, it is necessary to adapt the parameters to your system configuration.

Name Value

Internal

Value

Internal

Value, Type

Default Min. Max. EDS Slot Index
Module ID Internal 6135 *1) WORD

6135

0x17F7

0 65535 xx01
Ignore module

No

Yes

0

1

BYTE

No

(0x00)

     
Parameter length Internal 1 BYTE 0 0 255 xx02 *2)

*1) with CS31 and addresses less than 70, the value is increased by 1

*2) Value is hexadecimal: HighByte is slot (xx: 0 … 7), LowByte is index (1 … n)

GSD file:

Ext_User_Prm_Data_Len =

Ext_User_Prm_Data_Const(0) =

  1. =

0x03

0xF8, 0x17, 0x00,\

0x01;