Technical data

The System Data of AC500 and S500 are valid for standard version System Data AC500.

The System Data of AC500-XC are valid for the XC version System Data AC500-XC.

Only additional details are therefore documented below.

Process supply voltage  
Connections Terminals 1.8, 2.8, 3.8 and 4.8 for UP (+24 V DC) and 1.9, 2.9, 3.9 and 4.9 for ZP (0 V)
Protection against reverse voltage Yes
Rated protection fuse at UP 10 A fast
Rated value 24 V DC
Max. ripple 5 %
Current consumption  
From UP 0.07 A + max. 0.008 A per input + max. 0.5 A per output + 0.01 A for A, B and Z inputs
Via I/O-Bus Ca. 5 mA
Inrush current from UP (at power-up) 0.04 A²s
Electrical isolation Yes, per module
Max. power dissipation within the module 6 W (outputs unloaded)
Weight (without Terminal Unit) Ca. 125 g
Mounting position Horizontal mounting or vertical with derating (output load reduced to 50 % at 40 °C)
Cooling The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet.

Note

All I/O channels are protected against reverse polarity, reverse supply, short circuit and continuous overvoltages up to 30 V DC.