Technical data of the fast outputs (SSI CLK output \ B0, \ B1 \ for optical interface)

Number of channels 2
Reference potential for all outputs Terminals 1.9…4.9  (minus pole of the process supply voltage, signal name ZP)
Common power supply voltage For all outputs: terminals 1.8…4.8 (plus pole of the process supply voltage, signal name UP)
Output voltage for signal 0 ≤ 1.5 V at 10 mA
Output delay (0->1 or 1->0) Typ. 0.3 µs
Output current ≤ 10 mA
Switching frequency < 1 Mhz (depending on firmware)
Short-circuit proof / overload proof Yes
Output current limitation Yes, automatic reactivation after short-circuit/overload
Resistance to feedback against 24V signals Yes
Resistance to feedback against reverse polarity No
Max. cable length (shielded) Typ. 12.5 m @ 500 kHz (depending on sensor)