Parameterization

The arrangement of the parameter data is depending on the firmware version installed inside the CPUs and Bus Modules:

Firmware version Mounting position Configuration
Firmware version < V2.0.0
  • I/O Module connected locally to a CPU
  • I/O Module connected to CS31 Bus Module
The arrangement of the parameter data is performed by PLC-Configuration inside Control Builder software.
  • I/O Module connected remotely to a Bus Module (not CS31)
The arrangement of the parameter data is performed by your master configuration software SYCON.net in connection with the S500 GSD files and in conjunction with the Control Builder software.
Firmware version > V2.0.0
  • All
The arrangement of the parameter data is performed by Control Builder Plus software.

The parameter data directly influences the functionality of modules.

For non-standard applications, it is necessary to adapt the parameters to your system configuration.

Name Value Internal Value Internal value, Type Default Min. Max. EDS Slot Index
Module ID Intern 1805 *1) WORD 0x070D 0 65535 0x0Y01
Ignore module *2)

No

Yes

0

1

BYTE

No

0x00

    Not for FBP
Parameter length Internal 6 BYTE 0 0 255 xx02 *3)
Check supply

Off

On

0

1

BYTE

On

0x01

    0x0Y03
Input delay

0.1 ms

1 ms

8 ms

32 ms

0

1

2

3

BYTE

8 ms

0x02

0 3 0x0Y04
Mode Counter 0 see table below 0 BYTE 0x00 0 15 0x0Y05
Counter 0 frequency limit

No filter

50 Hz

500 Hz

5 kHz

20 kHz

0

1

2

3

4

BYTE

No filter

0x00

0 4 0x0Y06
Counter 0 input level

0-24 V DC

0-5 V DC

Differential

1 Vpp sinus

0

1

2

3

BYTE 0-24 V DC 0x00 0 3 0X0Y07
SSI 0 frequency

200 kHz

500 kHz

1 MHz

2

3

4

BYTE

200 kHz

0x02

0 4 0x0Y08
SSI 0 resolution (in bit) 8 to 32 bit   BYTE

16 bit

16

8 32 0x0Y09
SSI 0 code type Binary 0 BYTE

Binary

0

0 0 0x0Y0A
SSI 0 polling time 10 ms   BYTE 10 1 255 0x0Y0B
5 V sensor 0 supply

Off

On

0 BYTE

Off

0x00

0 1 0x0Y0C
Mode Counter 1 see table below 0 BYTE 0x00 0 15 0x0Y0D
Counter 1 frequency limit

No filter

50 Hz

500 Hz

5 kHz

20 kHz

0

1

2

3

4

BYTE

No filter

0x00

0 4 0x0Y0E
Counter 1 input level

0-24 V DC

0-5 V DC

Differential

1 Vpp sinus

0

1

2

3

BYTE 0-24 V DC 0x00 0 3 0X0Y0F
SSI 1 frequency

200 kHz

500 kHz

1 MHz

2

3

4

BYTE

200 kHz

0x02

2 4 0x0Y10
SSI 1 resolution (in bit) 8 to 32 bit   BYTE

16 bit

16

8 32 0x0Y11
SSI 1 code type Binary 0 BYTE

Binary

0

0 0 0x0Y12
SSI 1 polling time 10 ms   BYTE 10 1 255 0x0Y13
5 V sensor 1 supply

Off

On

0 BYTE

Off

0x00

0 1 0x0Y14
Detection SC on sensors

Off

On

0 BYTE

Off

0x00

0 1 0x0Y15
Output behaviour com fault

Off

Last value

Substitute

Last value 5s

Substitute 5s

Last value 10s Substitute 10s

0

1

2

3

4

5

6

BYTE

Off

0x00

0 1 0x0Y16
Substitute value 0 0 WORD

Default

0x0000

0 65536 0x0Y17

*1) with CS31 and addresses less than 70 and FBP, the value is increased by 1

*2) Not with FBP

*3) Value is hexadecimal: HighByte is slot (xx: 0 … 7), LowByte is index (1 … n)

Operating modes for counters 0 and 1, configuration table:

Internal value Operating modes of counter
0 No counter / No PWM (default value)
1 1-1 UpDown counter (A)
2 2-1 UpDown with release input
3 3-2 UpDown counters (A, B)
4 4-2 UpDown (A, B on falling edges)
5 5-1 UpDown dynamic set (B) / rising edge
6 6-1 UpDown dynamic set (B) / falling edge
7 Not used
8 8-1 UpDown with release (B), 0 cross detection
9 - 19 Not used
20 11-1 Incremental encoder
21 12-2 Incremental encoder X2
22 13-1 Incremental encoder X4
30 14-1 SSI, absolute encoder
40 15-1 Time frequency meter
GSD file:

Ext_User_Prm_Data_Len =

Ext_User_Prm_Data_Const(0) =

25

0x07, 0x0E, 0x17, \

0x01, 0x02, \

0x00, 0x00, 0x00, 0x02, 0x10, 0x00, 0x0A, 0x00, \

0x00, 0x00, 0x00, 0x02, 0x10, 0x00, 0x0A, 0x00, \

0x00, 0x00, 0x00, 0x00;