Parameterization¶
The arrangement of the parameter data is depending on the firmware version installed inside the CPUs and Bus Modules:
| Firmware version | Mounting position | Configuration | 
|---|---|---|
| Firmware version < V2.0.0 | 
  | 
The arrangement of the parameter data is performed by PLC-Configuration inside Control Builder software. | 
  | 
The arrangement of the parameter data is performed by your master configuration software SYCON.net in connection with the S500 GSD files and in conjunction with the Control Builder software. | |
| Firmware version > V2.0.0 | 
  | 
The arrangement of the parameter data is performed by Control Builder Plus software. | 
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configuration.
Module: Module slot address: Y = 1…7
| Nr. | Name | Value | Internal value  | 
Internal value, type  | 
Default | Min. | Max. | EDS Slot/Index  | 
|---|---|---|---|---|---|---|---|---|
| 1 | Module ID | Internal | 1000 *1)  | 
Word | 1000 0x03E8  | 
0 | 65535 | 0x0Y01 | 
2 *2)  | 
Ignore module | No Yes  | 
0 1  | 
Byte | No 0x00  | 
not for FBP | ||
| 3 | Parameter length | Internal | 3-CPU 2-FBP  | 
Byte | 3 2  | 
0 | 255 | 0x0Y02 | 
| 4 | Check supply | Off on  | 
0 1  | 
Byte | On 0x01  | 
0 | 1 | 0x0Y03 | 
| 5 | Input delay | 0.1 ms 1 ms 8 ms 32 ms  | 
0 1 2 3  | 
Byte | 8 ms 0x02  | 
0 | 3 | 0x0Y04 | 
6 *4)  | 
Fast counter | 0 : 10 *3)  | 
0 : 10  | 
Byte | Mode 0 0x00  | 
not for FBP | 
*1) With CS31 and addresses less than 70 and FBP, the value is increased by 1
*2) Not with FBP
*3) Counter operating modes Fast Counter, see description of the Fast Counter Fast Counter
*4) With FBP or CS31 without the parameter Fast counter
Note
The Fast Counter of the module does not work if the module is connected to a
- FBP Interface Module
 - CS31 Bus Module
 - CANopen Bus Module
 
| GSD file: | Ext_User_Prm_Data_Len = Ext_User_Prm_Data_Const(0) =  | 
5 0x03, 0xe9, 0x02, \ 0x01, 0x02;  |