Technical Data

The System Data of AC500 and S500 System Data AC500 are valid for standard version.

The System Data of AC500-XC System Data AC500-XC are valid for the XC version.

Only additional details are therefore documented below.

Process supply voltage UP  
  Connections Terminals 1.8, 2.8, 3.8 and 4.8 for +24 V (UP) as well as 1.9, 2.9, 3.9 and 4.9 for 0 V (ZP)
  Rated value 24 V DC
  max. ripple 5 %
  Protection against reversed voltage yes
  Rated protection fuse for UP 10 A fast
  Electrical isolation yes, per module
Current consumption  
  from 24 V DC power supply at the terminals UP/L+ and ZP/M of the CPU/Bus Module ca. 2 mA
  from UP at normal operation 0.15 A
  inrush current from UP (at power up) 0.008 A²s
Weight (without Terminal Unit) ca. 105 g
Mounting position horizontal or vertical with derating (output load reduced to 50 % at 40°C per group)
Cooling The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet.

Note

All I/O channels (digital and analog) are protected against reverse polarity, reverse supply, short circuit and continuous overvoltage up to 30 V DC.