Technical Data¶
The System Data of AC500 and S500 System Data AC500 are valid for standard version.
The System Data of AC500-XC System Data AC500-XC are valid for the XC version.
Only additional details are therefore documented below.
| Process supply voltage UP | ||
| Connections | Terminals 1.8, 2.8, 3.8 and 4.8 for +24 V (UP) as well as 1.9, 2.9, 3.9 and 4.9 for 0 V (ZP) | |
| Rated value | 24 V DC | |
| max. ripple | 5 % | |
| Protection against reversed voltage | yes | |
| Rated protection fuse for UP | 10 A fast | |
| Electrical isolation | yes, per module | |
| Current consumption | ||
| from 24 V DC power supply at the terminals UP/L+ and ZP/M of the CPU/Bus Module | ca. 2 mA | |
| from UP at normal operation | 0.15 A | |
| inrush current from UP (at power up) | 0.008 A²s | |
| Weight (without Terminal Unit) | ca. 105 g | |
| Mounting position | horizontal or vertical with derating (output load reduced to 50 % at 40°C per group) | |
| Cooling | The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet. | |
Note
All I/O channels (digital and analog) are protected against reverse polarity, reverse supply, short circuit and continuous overvoltage up to 30 V DC.