Technical Data of the Module¶
Process supply voltages UP/UP3 | ||
Rated value | 24 V DC (for inputs and outputs) | |
Max. load for the terminals | 10 A | |
Protection against reversed voltage | Yes | |
Rated protection fuse on UP/UP3 | 10 A fast | |
Electrical isolation | Ethernet interface against the rest of the module | |
Inrush current from UP (at power up) | On request | |
Current consumption via UP (normal operation) | 0.2 A | |
Current consumption via UP3 | 0.06 A + 0.5 A max. per output | |
Connections | Terminals 1.8 and 2.8 for +24 V (UP) Terminal 3.8 for +24 V (UP3) Terminals 1.9, 2.9 and 3.9 for 0 V (ZP) |
|
Max. power dissipation within the module | 6 W | |
Number of digital inputs | 8 | |
Number of digital outputs | 8 | |
Number of analog inputs | 4 | |
Number of analog outputs | 2 | |
Reference potential for all digital inputs and outputs | Minus pole of the supply voltage, signal name ZP | |
Setting of the IO Device identifier | With 2 rotary switches at the front side of the module | |
Diagnose | See Diagnosis and Displays PROFINETâ IO Bus Module CI501-PNIO (V3) | |
Operation and error displays | 32 LEDs (totally) | |
Weight (without Terminal Unit) | ca. 125 g | |
Mounting position | Horizontal Or vertical with derating (output load reduced to 50 % at 40 °C per group) |
|
Extended ambient temperature (XC version) | >60 °C on request | |
Cooling | The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet. |
Note