Group parameters for the digital part

Name Value

Internal

Value

Internal

Value, type

Default
Input delay

0.1 ms

1 ms

8 ms

32 ms

0

1

2

3

BYTE

0.1 ms

0x00

Detect short circuit at outputs

Off

On

0

1

BYTE

On

0x01

Behaviour DO at comm. error *)

Off

Last value

Last value 5 sec

Last value 10 sec

Substitute value

Substitute value 5 sec

Substitute value 10 sec

0

1

6

11

2

7

12

BYTE

Off

0x00

Substitute value at output 0 … 255 00h … FFh BYTE

0

0x0000

Detect voltage overflow at outputs **)

Off

On

0

1

BYTE

On

0x01

*) The parameters Behaviour DO at comm. error is only analyzed if the Failsafe-mode is ON.

**) The status “externally voltage detected” appears, if the output of a channel DC0..DC7 should be switched on while an externally voltage is connected PROFINETâ IO Bus Module CI501-PNIO (V3). In this case the start up is disabled, as long as the externally voltage is connected. The monitoring of this state and the resulting diagnosis message can be disabled by setting the parameters to “OFF”.