Displays

Statuses of the LEDs:
LED Status Color LED = OFF LED = ON LED Flashes
PWR System voltage green System firmware is not running System firmware is running
CS31 A CS31 communication green No communication at CS31 Bus A Communication at CS31 Bus A OK 10 Hz: Not bit lifetime management
C. B CS31 communication green No communication at CS31 Bus B Communication at CS31 Bus B OK 10 Hz: Not bit lifetime management
S-ERR Sum Error red Internal error detected 2 Hz: Diagnostic event happened
I/O-Bus Communication via the I/O Bus green No I/O Bus communication Expansion modules connected 2 Hz: Error I/O-Bus
RUN A CPU active green CPU A is not primary CPU A is primary

RUN B LED off:

CI590-CS31-HA primary self selection. No primary order from both PLC. PLC A has been selected as primary.

RUN B LED on: 2 primary orders. PLC B is primary.

R. B CPU active green CPU B is not primary CPU B is primary

RUN A LED off:

CI590-CS31-HA primary self selection. No primary order from both PLC. PLC B has been selected as primary.

RUN A LED on: 2 primary orders. PLC A is primary.

SYNC-ERR Outputs from CPU A and CPU B red Configuration conflict detected

10 Hz: Not parameterized

2 Hz: Switch-over has occured

C0 … C15 Digital inputs/outputs yellow Input/output = OFF Input/output = ON (the input voltage is even displayed if the supply voltage is OFF)
UP Process supply voltage and initialization green Process voltage is missing

Process voltage

OK and initialization completed

Module was not initialized correctly
CH-ERR3   red No error Serious error within the corresponding group Error on one channel of the corresponding group (e.g. short-circuit at an output)
CH-ERR4   red No error Serious error within the corresponding group Error on one channel of the corresponding group (e.g. short-circuit at an output)
CH-ERR *) Module error red No error or process voltage is missing Internal error
*) All LEDs CH-ERR2 to CH-ERR4 light up together