| Number of channels per module |
2 configurable voltage or current outputs |
| Distribution of channels into groups |
1 (2 channels per group) |
| Connection of the signals O0U- and O1U+ |
Terminals 13 and 15 |
| Connection of the signals O0I+ and O1I+ |
Terminals 14 and 16 |
| Output type |
Bipolar with voltage, unipolar with current |
| Resolution |
12 bits or 11 bits plus sign |
| Accuracy |
|
| |
Typical (at 25 °C) |
±0.5 % of full scale |
| |
Worst case (at 0 °C … +60 °C or EMC disturbances) |
±2 % of full scale |
| Indication of the output signals |
No |
| Output Resistance (load) as current output |
0 … 500 W |
| Output load ability as voltage output |
±2 mA max. |
| Relationship between input signal and hex code |
table Analog Output Module AO561 |
| Unused outputs |
Must not be connected and must be configured as “unused” |
| Overvoltage protection |
Yes, up to 30 V DC |
| Max. cable length (conductor cross section > 0,14 mm²) |
|
| |
Unshielded wire |
10 m |
| |
Shielded wire |
100 m |