Technical Data

The System Data of AC500 and S500 System Data AC500 are valid for standard version.

The System Data of AC500-XC System Data AC500-XC are valid for the XC version.

Only additional details are therefore documented below.

Protocol CANopen® slave
Technology Hilscher netX100
Usable CPUs PM57x, PM58x, PM59x PM57x (-y), PM58x (-y) and PM59x (-y)
Usable Terminal Bases All TB5xx TB51x-TB54x
Bus connection Pluggable connector COMBICON, 2x5-pole
Internal power supply Via the Communication Module Interface of the Terminal Base
Transfer rate 10 kBit/s to 1 MBit/s
Transfer method According to CAN standard
Bus length (segment length max.) According to table: Maximum cable length within a CANopen® field bus
Indicators 5 LEDs
Ambient temperature 0 °C … +60 °C
Extended ambient temperature (XC version) -30 °C … +70 °C
Current consumption from 24 V DC power supply at the Terminal Base of the CPU Ca. 50 mA
Weight Ca. 150 g
Ambient temperature

see:

System data AC500 System Data AC500

System Data AC500 XC System Data AC500-XC

Adjusting elements None
Quantity of input and output data per I/O Device Max. 512 byte (respectively for input and output)
Supported protocol services

NMT slave

PDO

SDO server

Heartbeat

Nodeguard

Min. bus cycle 1 ms