Technical Data¶
The System Data of AC500 and S500 System Data AC500 are valid for standard version.
The System Data of AC500-XC System Data AC500-XC are valid for the XC version.
Only additional details are therefore documented below.
Protocol | CANopen® slave |
Technology | Hilscher netX100 |
Usable CPUs | PM57x, PM58x, PM59x PM57x (-y), PM58x (-y) and PM59x (-y) |
Usable Terminal Bases | All TB5xx TB51x-TB54x |
Bus connection | Pluggable connector COMBICON, 2x5-pole |
Internal power supply | Via the Communication Module Interface of the Terminal Base |
Transfer rate | 10 kBit/s to 1 MBit/s |
Transfer method | According to CAN standard |
Bus length (segment length max.) | According to table: Maximum cable length within a CANopen® field bus |
Indicators | 5 LEDs |
Ambient temperature | 0 °C … +60 °C |
Extended ambient temperature (XC version) | -30 °C … +70 °C |
Current consumption from 24 V DC power supply at the Terminal Base of the CPU | Ca. 50 mA |
Weight | Ca. 150 g |
Ambient temperature | see: System data AC500 System Data AC500 System Data AC500 XC System Data AC500-XC |
Adjusting elements | None |
Quantity of input and output data per I/O Device | Max. 512 byte (respectively for input and output) |
Supported protocol services | NMT slave PDO SDO server Heartbeat Nodeguard |
Min. bus cycle | 1 ms |