Output Description¶
DONE
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
BOOL | - | - | - |
DONE indicates the processing state of the function block. After completion or abortion of processing due to an error, DONE is set to TRUE for one cycle. This output always has to be considered together with output ERR. If ERR is TRUE, an error occurred. In this case, the error number can be read at output ERNO.
ERR (error)
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
BOOL | - | - | - |
ERR indicates whether an error occurred during the processing of the function block. This output always has to be considered together with output DONE. If DONE is TRUE and ERR is TRUE, an error occurred. In this case, the error number can be read at output ERNO.
ERNO (error \ number)
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
WORD | - | - | - |
ERNO provides an error identifier if an invalid value has been applied to an input or if an error occurred during job processing. ERNO has to be considered together with the outputs DONE and ERR. The value output at ERNO is only valid if DONE is TRUE and ERR is TRUE Error Messages of the Function Block Libraries.
DIAG (diagnosis)
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
BYTE | - | 0 16#01 = 1 -> Watchdog error |
- |
Output displays the diagnosis message of the DC541. If DIAG is 0, no diagnosis message is available. The following messages are possible:
OV0…OV7 (overload \ C0…C7)
Data_Type | Default_Value | Range | Unit |
---|---|---|---|
BOOL | - | - | - |
The outputs OV0..OV7 display the current output status of the channels C0…C7. If the respective bit is TRUE, the corresponding output cannot be switched e.g. due to an overload or a short circuit.