Channel parameters for the cam switch (max. 32x)

Name Value

Internal

value

Internal

value, type

Default
camToTrack0 *1) 0 … 15 0 … 15 BYTE FF
: : : : :
camToTrack31 0 … 15 0 … 15 BYTE FF

*1) The value of the parameter camToTrack#  defines which DO (digital output) is assigned to the track. camToTrack0 = 3 for example means that track 0 is assigned to the digital output 3. If the value FFh is set to a track, no digital output is assigned to it.

Name Value Referred FB from extended Cam Switch Library *2

Internal

value

Internal

value, type

camType[0]

*1)

Common

Pulsed

Timed

Comfort

Cam shift

Binary shift

Multiturn cam

Time timed

Reference

Multiturn timed

MCX_CamSwitchSimple_c MCX_CamSwitchSimple_c,

MCX_CamSwitchSimple_dc MCX_CamSwitchSimple_DC,

MCX_PulseSwitch_dc MCX_PulseSwitch_DC

MCX_CamSwitchTimed_dc MCX_CamSwitchTimed_DC

MCX_CamSwitchComfort_dc MCX_CamSwitchComfort_DC

MCX_CamShift_dc MCX_CamShift_DC

MCX_BinaryShift_dc MCX_BinaryShift_DC

MCX_CamSwitchMulti_dc MCX_CamSwitchMulti_DC

MCX_SwitchTimeTimed_dc MCX_CamSwitchTimed_DC

MCX_BinaryReference_dc MCX_BinaryReference_DC

MCX_CamSwitchMultiTimed_d MCX_CamSwitchMultiTimed_DCc

0

1

2

3

4

5

6

7

8

9

BYTE

*1) camType additionally to camToTrack identifies the type of each cam switch and enables the use of a specific Function Block from the Extended Cam Switch Library.

*2) camType parameters and the Extended Cam Switch Library are only available for CI511-ETHCAT and CI512-ETHCAT with device index C0 and above.