Technical Data of the Digital \ Outputs¶
Number of channels per module | 8 | |
Distribution of the channels into groups | 1 group of 8 channels | |
Terminals of the channels DO0 to DO7 | Terminals 3.0 to 3.7 | |
Reference potential for all outputs | Terminals 1.9…3.9 (minus pole of the supply voltage, signal name ZP) | |
Common power supply voltage | For all outputs terminal 3.8 (plus pole of the supply voltage, signal name UP3) | |
Output voltage for signal 1 | UP3 (-0.8 V) | |
Output delay (0->1 or 1->0) | On request | |
Output current | ||
Rated value per channel | 500 mA @ UP3 = 24 V | |
Max. value (all channels together) | 4 A | |
Leakage current with signal 0 | < 0.5 mA | |
Fuse for UP3 | 10 A fast | |
Demagnetization with inductive DC load | Via internal varistors (see figure below this table) | |
Output switching frequency | ||
With resistive load | On request | |
With inductive loads | Max. 0.5 Hz | |
With lamp loads | 11 Hz max. @ 5 W max. | |
Short-circuit proof / overload proof | Yes | |
Overload message (I > 0.7 A) | Yes, after ca. 100 ms | |
Output current limitation | Yes, automatic reactivation after short-circuit/overload | |
Resistance to feedback against 24V signals | Yes (software-controlled supervision) | |
Max. cable length | ||
Shielded | 1000 m | |
Unshielded | 600 m |
The following drawing shows the circuitry of a digital input/output with the varistors for demagnetization when inductive loads are switched off.
Digital input/output (circuit diagram)
Figure: