Module ParameterΒΆ
Name | Value | Internal Value |
Internal Value, type |
Default |
---|---|---|---|---|
Module ID | Internal | 49435 | WORD | 49435 |
Parameter length | Internal | 10 | BYTE | 10 |
Error LED / Failsafe function *1) | On Off by E4 Off by E3 On + failsafe Off by E4 + failsafe Off by E3 + failsafe |
0 1 3 16 17 19 |
BYTE | 0 |
Check Supply | off on |
0 1 |
BYTE | 1 |
*1) | Setting | Meaning |
---|---|---|
On | Error-LED lights up at errors of all error classes, Failsafemode off | |
Off by E4 | Error LED lights up at errors of error classes E1, E2 and E3, Failsafemode off | |
Off by E3 | Error LED lights up at errors of error classes E1 and E2 auf, Failsafemode off | |
On + failsafe | Error-LED lights up at errors of all error classes, Failsafemode on* | |
Off by E4 + failsafe | Error LED lights up at errors of error classes E1, E2 and E3, Failsafemode on* | |
Off by E3 + failsafe | Error LED lights up at errors of error classes E1 and E2, Failsafemode on* |
*) The parameter behaviourDOatCommunicationFault is only analyzed if the Failsafe-mode is ON.