Module ParameterΒΆ
| Name | Value | Internal Value |
Internal Value, type |
Default |
|---|---|---|---|---|
| Module ID | Internal | 49435 | WORD | 49435 |
| Parameter length | Internal | 10 | BYTE | 10 |
| Error LED / Failsafe function *1) | On Off by E4 Off by E3 On + failsafe Off by E4 + failsafe Off by E3 + failsafe |
0 1 3 16 17 19 |
BYTE | 0 |
| Check Supply | off on |
0 1 |
BYTE | 1 |
| *1) | Setting | Meaning |
|---|---|---|
| On | Error-LED lights up at errors of all error classes, Failsafemode off | |
| Off by E4 | Error LED lights up at errors of error classes E1, E2 and E3, Failsafemode off | |
| Off by E3 | Error LED lights up at errors of error classes E1 and E2 auf, Failsafemode off | |
| On + failsafe | Error-LED lights up at errors of all error classes, Failsafemode on* | |
| Off by E4 + failsafe | Error LED lights up at errors of error classes E1, E2 and E3, Failsafemode on* | |
| Off by E3 + failsafe | Error LED lights up at errors of error classes E1 and E2, Failsafemode on* |
*) The parameter behaviourDOatCommunicationFault is only analyzed if the Failsafe-mode is ON.