Technical Data¶

The System Data of AC500 and S500 System Data AC500 are valid for standard version.

The System Data of AC500-XC System Data AC500-XC are valid for the XC version.

Only additional details are therefore documented below.

Communication Module CM598-CN  
Protocol CANopenâ Master, CAN2A, CAN2B
Transmission rate 10 kBit/s to 1 MBit/s
Usable CPUs PM57x, PM58x, PM59x PM57x (-y), PM58x (-y) and PM59x (-y)
Usable Terminal Bases All TB5xx TB51x-TB54x
Field bus connector Pluggable connector COMBICON, 5-pole
Technology Hilscher netX100
Indicators 5 LEDs
Ingress protection IP20
Internal power supply Via the Communication Module interface of the Terminal Base
Current consumption from 24 V DC power supply at the Terminal Base of the CPU Typ. 100 mA
Number of Slaves Max. 126
Number of receive/transmit PDOs Max. 512 (respectively for receive and transmit)
Total quantity of input and output data Max. 3584 byte (respectively for input and output)
Bus configuration Done with Automation Builder
Weight Ca. 150 g