Connecting the DC551-CS31 and S500 I/O devices to the \ CS31 bus

The base module “DC551-CS31” is available in two versions in the PLC configuration:

  1. DC551-CS31 8 DI + 16 DC / without fast counter

    The addresses 00…61 can be set at the module and in the PLC configuration.

  2. DC551-CS31 8 DI + 16 DC + 2FC / with 2 fast counters

    The hardware addresses 70…99 can be set at the module. This corresponds to the module addresses 00…29 with activated counter. In the PLC configuration and at the block CNT_DC551, the module address (00..29) is set.(link to module description Contents).

The following parameters can be set in the PLC configuration for the DC551-CS31:

../_images/e57be040e38c566e0a33139000eba54e
Parameter Default value Value Meaning
Ignore module see remark 1 No No It is checked whether the module exists on the CS31 bus.
Yes

Module is not checked.

-> available as of CPU firmware V1.2.0 and PS501 V1.2

Module address 0 0…69 Module address of the DC551-CS31 without fast counter
0…29 Module address of the DC551-CS31 with fast counter
Error-LED see remark 2 On On The error LED lights up for errors of all classes, no failsafe function activated.
Off_by_E4 Warnings (E4) are not indicated by the error LED, no failsafe function activated.
Off_by_E3

Warnings (E4) and light errors (E3) are not indicated by the error LED.

No failsafe function activated.

On+failsafe

The error LED lights up for errors of all classes and the failsafe function of the CS31 bus is activated.

-> available as of CPU firmware V1.2.0, DC551-CS31 firmware V1.9 and PS501 V1.2

Off_by_E4+failsafe

Warnings (E4) are not indicated by the error LED, the failsafe function of the CS31 bus is activated.

-> available as of CPU firmware V1.2.0, DC551-CS31 firmware V1.9 and PS501 V1.2

Off_by_E3+failsafe

Warnings (E4) and light errors (E3) are not indicated by the error LED, the failsafe function of the CS31 bus is activated.

-> available as of CPU firmware V1.2.0, DC551-CS31 firmware V1.9 and PS501 V1.2

Check supply On On Control voltage monitoring ON
Off Control voltage monitoring OFF
Input delay 8 ms 0.1 / 1 / 8 / 32 ms Input delay 0.1 / 1 / 8 / 32 ms
Fast counter 0-No counter 0-No counter

Operation mode of the fast counter

(Link to hardware / description of fast counters Fast Counter)

Detection short-circuits at outputs On On Output short-circuit detection ON
Off Output short-circuit detection OFF
Behaviour of outputs at communication fault see remark 2 Off Off Behavior of outputs at communication faults on the CS31 bus OFF
Last value

Last value

-> available as of CPU firmware V1.2.0, DC551-CS31 firmware V1.9 and PS501 V1.2

Substitute value

Substitute value

-> available as of CPU firmware V1.2.0, DC551-CS31 firmware V1.9 and PS501 V1.2

Last value 5 sec.

Last value for 5 seconds

-> available as of CPU firmware V1.2.0, DC551-CS31 firmware V1.9 and PS501 V1.2

Substitute value 5 sec.

Substitute value for 5 seconds

-> available as of CPU firmware V1.2.0, DC551-CS31 firmware V1.9 and PS501 V1.2

Last value 10 sec.

Last value for 10 seconds

-> available as of CPU firmware V1.2.0, DC551-CS31 firmware V1.9 and PS501 V1.2

Substitute value 10 sec.

Substitute value for 10 seconds

-> available as of CPU firmware V1.2.0, DC551-CS31 firmware V1.9 and PS501 V1.2

Substitute

value see remark 2

0

0…65535

0000hex…FFFFhex

Substitute value for the outputs, one bit per output, bit 0=C8 .. bit 15=C23

-> available as of CPU firmware V1.2.0, DC551-CS31 firmware V1.9 and PS501 V1.2