Number of channels per module |
16 transistor outputs (24 V DC, 0.5 A max.) |
Distribution of the channels into groups |
1 (16 channels per group) |
Connection of the channels O0 to O7 |
Terminals 1 to 9 |
Connection of the channels O8 to O15 |
Terminals 11 to 18 |
Common power supply voltage |
Terminal 19 (plus pole of the process voltage, signal name UP) |
Reference potential for the channels O0 to O15 |
Terminal 20 (minus pole of the process voltage, signal name ZP) |
Indication of the output signals |
1 yellow LED per channel; the LED is on when the output signal is high (signal 1) and the module is powered through the I/O-Bus |
Way of operation |
Non-latching type |
Min. output voltage at signal 1 |
UP -0.3 V at max. current consumption |
Output delay (max. at rated load) |
|
0 to 1 |
50 µs |
1 to 0 |
200 µs |
Output current |
|
Rated current per channel (max.) |
0.5 A at UP 24 V DC |
Rated current per group (max.) |
8 A |
Lamp load (max.) |
5 W |
Max. leakage current with signal 0 |
0.5 mA |
Rated protection fuse (for each channel) |
3 A fast |
Demagnetization when inductive loads are switched off |
Must be performed externally according to driven load specification |
Switching Frequencies |
|
With inductive loads |
Max. 0.5 Hz |
With lamp loads |
Max. 11 Hz at max. 5 W |
Short circuit / Overload proof |
No |
Overload message |
No |
Output current limitation |
No |
Resistance to feedback against 24 V DC |
No |
Connection of 2 outputs in parallel |
Not possible |
Max. cable length |
|
Shielded |
500 m |
Unshielded |
150 m |