| Number of channels per module | 
8 transistor inputs (24 V DC) | 
| Distribution of the channels into groups | 
1 group for 8 channels | 
| Electrical isolation | 
Yes, per group | 
| Connections of the channels I0 to I7 | 
Terminals 2 to 9 | 
| Reference potential for the channels I0 to I7 | 
Terminal 1 | 
| Indication of the input signals | 
1 yellow LED per channel; the LED is ON when the input     signal is high (signal 1) and the module’s logic is in operation | 
| Input type according to EN 61131-2 | 
Type 1 source | 
Type 1 sink | 
| Input signal range | 
-24 V DC | 
+24 V DC | 
| Signal 0 | 
-5 V … +3 V | 
-3 V … +5 V | 
| Undefined signal | 
-15 V … - 5 V | 
+5 V … +15 V | 
| Signal 1 | 
-30 V … -15 V | 
+15 V … +30 V | 
| Ripple with signal 0 | 
Within -5 V … +3 V | 
Within -3 V … +5 V | 
| Ripple with signal 1 | 
Within -30 V … -15 V | 
Within +15 V … +30 V | 
| Input current per channel | 
  | 
| Input voltage +24 V | 
Typ. 5 mA | 
| Input voltage +5 V | 
Typ. 1 mA | 
| Input voltage +15 V | 
> 2.5 mA | 
| Input voltage +30 V | 
< 8 mA | 
| Max. permissible leakage current (at 2-wire proximity     switches) | 
1 mA | 
| Input delay (0->1 or 1->0) | 
Typ. 0.1 to 32 ms (configurable via software), default:     8 ms | 
| Max. cable length | 
  | 
| Shielded | 
500 m | 
| Unshielded | 
300 m |