Diagnosis

E1..E4 d1 d2 d3 d4

Identifier

000..063

AC500-Display <− Display in
Class Comp Dev Mod Ch Err PS501 PLC Browser
Class

Inter-

face

Device Module Channel

Error-

Identifier

Error message Remedy
Errors for Onboard I/O
Light errors
3 8 255 2 0 3 MaxWaitRun for onboard I/O Module has expired, when PLC is put into RUN state Reboot and try it again. If the error still exists, replace processor module for testing
3 8 255 3 0 26 Invalid configuration of onboard I/O Module, e. g. 2  input channels are configured as fast counter and interrupt input at the same time. Correct PLC configuration
Warnings
4 8 1 2 1 2 Invalid configuration value for PWM channel. Frequency / cycletime for the PWM channel of the 8DI+6DO and 8DI+6DO+2AI+1AO module are common and if both channel are configured for PWM, the frequency of the second channel must be set to 0. Correct frequency
4 8 1 2 0..1 4 PWM channel frequency or cycle time too high Correct frequency or cycle time
4 8 1 2 0..1 7 PWM channel frequency or cycle time too low Correct frequency or cycle time
4 8 1 2 0 52 Frequency on interrupt input pin too high and interrupt events are missed Correct frequency
4 8 255 2 0 26 PLC was put into RUN state, although a configuration error is present, because parameter Run on config fault is set to YES Correct PLC configuration
4 8 255 0 0 43 Unspecified or internal error occured Replace processor module