Parameterization¶
The arrangement of the parameter data is depending on the firmware version installed inside the CPUs and Bus Modules:
Firmware version | Mounting position | Configuration |
---|---|---|
Firmware version < V2.0.0 |
|
The arrangement of the parameter data is performed by PLC-Configuration inside Control Builder software. |
|
The arrangement of the parameter data is performed by your master configuration software SYCON.net in connection with the S500 GSD files and in conjunction with the Control Builder software. | |
Firmware version > V2.0.0 |
|
The arrangement of the parameter data is performed by Control Builder Plus software. |
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configuration.
Module slot address: Y = 1…7
Nr. | Name | Value | Internal value |
Internal value, type |
Default | Min. | Max. | EDS Slot/Index |
---|---|---|---|---|---|---|---|---|
1 | Module ID | Internal | 1220 *1) |
Word | 1220 0x04C4 |
0 | 65535 | 0x0Y01 |
2 *2) |
Ignore module | No Yes |
0 1 |
Byte | No 0x00 |
not for FBP | ||
3 | Parameter length | Internal | 7 | Byte | 7-CPU 6-FBP |
0 | 255 | 0x0Y02 |
4 | Check supply | Off on |
0 1 |
Byte | On 0x01 |
0 | 1 | 0x0Y03 |
5 | Input delay | 0.1 ms 1 ms 8 ms 32 ms |
0 1 2 3 |
Byte | 8 ms 0x02 |
0 | 3 | 0x0Y04 |
6 *4) |
Fast counter | 0 : 10 *3) |
0 : 10 |
Byte | Mode 0 0x00 |
not for FBP | ||
7 | Short-circuit detection of output or sensor supply | Off On |
0 1 |
Byte | On 0x01 |
0 | 1 | 0x0Y05 |
8 | Behaviour of outputs at communication errors | Off Last value Substitute value |
0 1+(n*5) 2+(n*5), n <= 2 |
Byte | Off 0x00 |
0 | 2 | 0x0Y06 |
9 | Substitute value at outputs Bit 15 = Output 15 Bit 0 = Output 0 |
0… 65535 |
0… 0xffff |
Word | 0 0x0000 |
0 | 65535 | 0x0Y07 |
*1) With CS31 and addresses less than 70 and FBP, the value is increased by 1
*2) Not with FBP
*3) Counter Operating Modes Fast Counter, see description of the Fast Counter Fast Counter
*4) With FBP or CS31 without the parameter Fast counter
Note
The Fast Counter of the module does not work if the module is connected to a
- FBP Interface Module
- CS31 Bus Module
- CANopen Bus Module
GSD file: | ||
DC522: | Ext_User_Prm_Data_Len = Ext_User_Prm_Data_Const(0) = |
9 0x04, 0xc5, 0x06, \ 0x01, 0x02, 0x01, 0x00, 0x00, 0x00; |