Technical Data¶
The System Data of AC500 and S500 System Data AC500 are valid for standard version.
The System Data of AC500-XC System Data AC500-XC are valid for the XC version.
Only additional details are therefore documented below.
Process supply voltage UP | ||
Connections | Terminals 1.8, 2.8, 3.8 and 4.8 for +24 V (UP) as well as 1.9, 2.9, 3.9 and 4.9 for 0 V (ZP) | |
Rated value | 24 V DC | |
Max. ripple | 5 % | |
Protection against reversed voltage | Yes | |
Rated protection fuse on UP | 10 A fast | |
Electrical isolation | Yes, per module | |
Current consumption | ||
From 24 V DC power supply at the L+/UP and M/ZP terminals of the CPU/Bus Module | Ca. 2 mA | |
From UP at normal operation / with outputs | 0.15 A + max. 0.5 A per output | |
Inrush current from UP (at power up) | 0.005A²s | |
Max. power dissipation within the module | 6 W (outputs unloaded) | |
Sensor power supply | ||
Connections | Terminals 1.0…1.3 = +24 V, 1.4…1.7 = 0 V Terminals 3.0…3.3 = +24 V, 3.4…3.7 = 0 V |
|
Voltage | 24 V DC with short-circuit and overload protection | |
Loadability | Terminals 1.0…1.3, in total max. 0.5 A Terminals 3.0…3.3, in total max. 0.5 A |
|
Weight (without Terminal Unit) | Ca. 125 g | |
Mounting position | Horizontal Or vertical with derating (output load reduced to 50 % at 40°C per group) |
|
Cooling | The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet. |
Note
All I/O channels (digital and analog) are protected against reverse polarity, reverse supply, short circuit and continuous overvoltage up to 30 V DC.