Technical Data

The System Data of AC500 and S500 System Data AC500 are valid for standard version.

The System Data of AC500-XC System Data AC500-XC are valid for the XC version.

Only additional details are therefore documented below.

Process supply voltage UP  
  Connections Terminals 1.8, 2.8, 3.8 and 4.8 for +24 V (UP) as well as 1.9, 2.9, 3.9 and 4.9 for 0 V (ZP)
  Rated value 24 V DC
  Max. ripple 5 %
  Protection against reversed voltage Yes
  Rated protection fuse on UP 10 A fast
  Electrical isolation Yes, per module
Current consumption  
  From 24 V DC power supply at the L+/UP and M/ZP terminals of the CPU/Bus Module Ca. 2 mA
  From UP at normal operation / with outputs 0.15 A + max. 0.5 A per output
  Inrush current from UP (at power up) 0.005A²s
Max. power dissipation within the module 6 W (outputs unloaded)
Sensor power supply  
  Connections

Terminals 1.0…1.3 = +24 V, 1.4…1.7 = 0 V

Terminals 3.0…3.3 = +24 V, 3.4…3.7 = 0 V

  Voltage 24 V DC with short-circuit and overload protection
  Loadability

Terminals 1.0…1.3, in total max. 0.5 A

Terminals 3.0…3.3, in total max. 0.5 A

Weight (without Terminal Unit) Ca. 125 g
Mounting position

Horizontal

Or vertical with derating (output load reduced to 50 % at 40°C per group)

Cooling The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet.

Note

All I/O channels (digital and analog) are protected against reverse polarity, reverse supply, short circuit and continuous overvoltage up to 30 V DC.