Configuration of the IP Data of the PM5xy-ETH Onboard Ethernet (>= \ CBP 2.4)

Note

The IP data are used with highest priority. Existing settings done by the display or any other method will be overwritten.

Double-click Ethernet -> ETHx to open the IP settings in the editor window:

../_images/a15fcd2745ff82b90a33139000eba54e1

The following parameters are available:

Parameter Default Value Meaning

Parameter

(Remark 1 Configuration of the IP Data of the PM5xy-ETH Onboard Ethernet (>= \ CBP 2.4))

Force IP Settings Enabled Disabled The IP data is not used. The device must be configured by another means of settings the IP data. Use IP data
Enabled The IP data set in this editor is used for the device.
DHCP Disabled Disabled The DHCP client services are disabled. A static IP address must be used. IP mode (+ DHCP)
Enabled The DHCP client services are enabled. The IP address of the device will be set by a DHCP server in the network.
IP address 0.0.0.0 Valid IP address IP address of the device. IP address
Subnetmask 255.255.255.0 Valid subnet mask Subnet mask for the device. Netmask
Default gateway 0.0.0.0 Valid gateway address Default gateway address for the device. Gateway
Link mode Auto negotiation Auto negotiation The link mode will be detected automatically. Link mode
10 Mbit Half-Duplex The link mode is statically set to 10 Mbit half-duplex.
10 Mbit Full-Duplex The link mode is statically set to 10 Mbit full-duplex.
100 Mbit Half-Duplex The link mode is statically set to 100 Mbit half-duplex.
100 Mbit Full-Duplex The link mode is statically set to 100 Mbit full-duplex.
ABBNetConfig protocol active Enabled Enabled Remote configuration: ABB NetConfig protocol is enabled.  
Disabled Remote configuration: ABB NetConfig protocol is disabled.

Remark 1: Generic Device Configuration View Parameters

Tab IP Settings Configuration shows a list of all available parameters which is only visible if parameter Show generic device configuration views is activated (open the Options dialog window with menu item Tools -> Options…, parameter is located under section Device editor):

../_images/fac3629645ff83170a33139000eba54e1