Technical DataΒΆ
The System Data of AC500-eCo System Data AC500-eCo are valid here. Only additional details are therefore documented below.
| Process supply voltage UP | |
| Connections | Terminal 19 for UP (+24 V DC) and terminal 20 for ZP (0 V) |
| Rated value | 24 V DC |
| Current consumption via UP terminal | 5 mA + max. 0.5 A per output |
| Max. ripple | 5 % |
| Inrush current | 0.000002 A:sup:2s |
| Protection against reversed voltage | Yes |
| Rated protection fuse for UP | Recommended; the outputs must be protected by an 3 A fast fuse |
| Current consumption from 24 V DC power supply at the L+/UP and M/ZP terminals of the CPU/Bus Module | Ca. 10 mA |
| Electrical isolation | Yes, between the output group and the rest oft module |
| Isolated groups | 1 (8 channels per group) |
| Surge-voltage (max.) | 35 V DC for 0.5 s |
| Max. power dissipation within the module | On request |
| Weight | Ca. 115 g |
| Mounting position | Horizontal or vertical |
| Cooling | The natural convection cooling must not be hindered by cable ducts or other parts in the switch-gear cabinet. |