LED Status Display
The LEDs are located at the front of module. There are 2 different groups:
- The 5 system LEDs (PWR,     STA1 DP, STA2 DP, S-ERR and I/O-Bus) show the operation status of the     module and display possible errors.
 
- The 29 process LEDs (UP,     UP3, inputs, outputs, CH-ERR1 to CH-ERR3) show the process supply voltage     and the statuses of the inputs and outputs and display possible errors.
 
Status of the 5 System-LEDs:
| LED | 
Color | 
OFF | 
ON | 
Flashing | 
| PWR/RUN | 
green | 
Process supply voltage missing | 
Internal supply voltage OK, module ready for communication     with IO Controller | 
Start-up / preparing communication | 
| yellow | 
— | 
— | 
— | 
| STA1-DP | 
green | 
— | 
PROFIBUSâ running | 
Invalid device parameters | 
| STA2-DP | 
red | 
No error | 
Bus timeout | 
No communication to Master | 
| S-ERR | 
red | 
No error | 
Internal error | 
– | 
| I/O-Bus | 
green | 
No expansion modules connected or communication error | 
Expansion modules connected and operational | 
— | 
Status of the 29 process LEDs:
| LED | 
Color | 
OFF | 
ON | 
Flashing | 
| DC0 to DC7 | 
yellow | 
Input/Output is OFF | 
Input/Output is ON | 
– | 
| DI8 to DI15 | 
yellow | 
Input is OFF | 
Input is ON (the input voltage is even displayed if the     supply voltage is OFF) | 
– | 
| DO8 to DO15 | 
yellow | 
Output is OFF | 
Output is ON | 
– | 
| UP | 
green | 
Process supply voltage missing | 
Process supply voltage OK and initialization finished | 
– | 
| UP3 | 
green | 
Process supply voltage missing | 
Process supply voltage OK | 
– | 
| CH-ERR1 to CH-ERR3 | 
red | 
No error or process supply voltage missing | 
Internal error | 
Error on one channel of the corresponding group |